Final | 11/1/2011 | 11/3/2011 | 11/3/2011 | P | PASS |
Eric Strole
|
|
|
I asked the builder to get the approved set to the job site. Phone #: ###-#### >> Inspection requested via web by Dustin Rich
|
Rough-in | 9/13/2011 | 9/13/2011 | 9/13/2011 | P | PASS |
Eric Strole
|
|
|
>> Inspection requested via web by Dustin Rich-need to insulate y's in crawl by final.
|
Rough-in | 9/12/2011 | 9/12/2011 | 9/12/2011 | P | FAIL |
Troy James
|
|
|
Builder is delivering approved Wight Soft Phone #: ###-#### >> Inspection requested via web by Dustin Rich balanced dampers are required to be at take-offs or branch fitting, need insulation shield to b-vent
|
Rough-in | 9/6/2011 | 9/7/2011 | 9/7/2011 | P | FAIL |
Eric Strole
|
|
|
>> Inspection requested via web by Dustin Rich-need manual j report on site for rough-in, duct blast test pass.
|
Pressure Test | 9/6/2011 | 9/7/2011 | 9/7/2011 | P | PASS |
Eric Strole
|
|
|
3:00 PLEASE!!!! >> Inspection requested via web by Dustin Rich-20 lb test pass.
|
Pressure Test | 9/6/2011 | 9/7/2011 | 9/6/2011 | A | CANC |
Troy James
|
|
|
chance will be there @ 11:00 for duct blaster >> Inspection requested via web by Dustin Rich Inspection cancelled from web by: Dustin Rich
|
Rough-in | 9/6/2011 | 9/7/2011 | 9/6/2011 | A | CANC |
Troy James
|
|
|
chance will be there @ 11:00 for duct blaster >> Inspection requested via web by Dustin Rich Inspection cancelled from web by: Dustin Rich
|
Final | 8/30/2011 | 8/31/2011 | 8/31/2011 | A | CANC |
Dixie Fellows
|
|
|
Phone #: ###-#### >> Inspection requested via web by Dustin Rich Inspection cancelled from web by: Dustin Rich
|