Final | 12/27/2011 | 12/27/2011 | 12/27/2011 | P | PASS |
Bill VanDegrift
|
|
|
|
Final | 12/21/2011 | 12/21/2011 | 12/21/2011 | P | NR |
Bill VanDegrift
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN need to get the resubmitted ACCA report approved prior to final inspection
|
Rough-in | 11/1/2011 | 11/1/2011 | 11/1/2011 | P | PASS |
Dixie Fellows
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN
|
Rough-in | 10/31/2011 | 10/31/2011 | 10/31/2011 | A | FAIL |
Bill VanDegrift
|
|
|
IMC602.2.1 materials with in plenums. Plastic piping with in the plenums do not meet the flame spread and smoke development index of 25/50.
|
Conference | 10/27/2011 | 10/28/2011 | 10/28/2011 | A | FAIL |
Bill VanDegrift
|
|
|
pvc in plenum
|
Conference | 10/26/2011 | 10/27/2011 | 10/27/2011 | A | CANC |
Bill VanDegrift
|
|
|
electricians have installed plenum rated wire! Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN
|
Rough-in | 10/25/2011 | 10/26/2011 | 10/26/2011 | A | FAIL |
Dixie Fellows
|
|
|
greg Phone #: ###-####...elec wires in r/a to be plenum rated
|
Rough-in | 10/7/2011 | 10/10/2011 | 10/10/2011 | A | PART |
Dixie Fellows
|
|
|
8:30 meet troy and Rob...ok for cover...no duct blaster required as all duct in conditioned space...no gas appliances to be installed
|
Conference | 10/7/2011 | 10/10/2011 | 10/10/2011 | A | DONE |
Troy James
|
|
|
Meet dixie and rob at 8:30 for a conference
|
Rough-in | 10/6/2011 | 10/7/2011 | 10/7/2011 | A | PEND |
Dixie Fellows
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN...meeting rob and troy mon am
|
Rough-in | 10/4/2011 | 10/4/2011 | 10/4/2011 | P | CANC |
Dixie Fellows
|
|
|
Lid Cover Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN...this job requires a manual J that was sent out with the bldg permit and plans
|