Final | 7/20/2012 | 7/23/2012 | 7/23/2012 | A | PASS |
Eric Strole
|
|
|
Please do final, any questions call Jason Phone #: ###-#### >> Inspection requested via web by Diane Myslivy
|
Rough-in | 5/30/2012 | 5/31/2012 | 5/31/2012 | A | PASS |
Eric Strole
|
|
|
20 lb gas test, rough-in pass. (NO DUCT BLAST AT THIS TIME)
|
Rough-in | 5/30/2012 | 5/30/2012 | 5/30/2012 | P | FAIL |
Eric Strole
|
|
|
need heat sheild on b-vent in joist space and insulate return in joist space.
|
Rough-in | 5/24/2012 | 5/29/2012 | 5/29/2012 | A | FAIL |
Eric Strole
|
|
|
please do rough in any quesitons contact Jason Phone #: ###-#### >> Inspection requested via web by Diane Myslivy-20 lb gas test pass. supply and return in overhead garage joist space needs an R-6 value. No duct blast at this time.
|