Final | 11/14/2012 | 11/14/2012 | 11/14/2012 | P | PASS |
Eric Strole
|
|
|
If any corrections please call Brian ###-####. Thanks, Andrea. Phone #: ###-#### x0000 >> Inspection requested via web by Andrea Creek
|
Pressure Test | 10/2/2012 | 10/3/2012 | 10/3/2012 | P | PASS |
Eric Strole
|
|
|
Brian Shoecraft ###-#### or Jeff Creek ###-####. Phone #: ###-#### >> Inspection requested via web by Andrea Creek-20 lb test pass.
|
Rough-in | 10/2/2012 | 10/3/2012 | 10/3/2012 | P | PASS |
Eric Strole
|
|
|
Brian Shoecraft ###-#### or Jeff Creek ###-####. Phone #: ###-#### >> Inspection requested via web by Andrea Creek
|
Pressure Test | 10/2/2012 | 10/2/2012 | 10/2/2012 | P | FAIL |
Eric Strole
|
|
|
Brian ###-#### or Jeff ###-####. Phone #: ###-#### x0000 >> Inspection requested via web by Andrea Creek-gas test fail.
|
Rough-in | 10/2/2012 | 10/2/2012 | 10/2/2012 | P | FAIL |
Eric Strole
|
|
|
Brian ###-#### or Jeff ###-####. Phone #: ###-#### x0000 >> Inspection requested via web by Andrea Creek-1-missing register 1st flr per manual-j. 2-some supply runs 1st flr are undersized per manual-j. 3- need to insulate return in garage joist space. 4-gas test fail.
|