Final | 6/12/2014 | 6/12/2014 | 6/12/2014 | P | PASS |
Chad Schwendiman
|
|
|
Cheryl Phone #: ###-####
|
Final | 2/14/2014 | 2/14/2014 | 2/14/2014 | P | PASS |
Dixie Fellows
|
|
|
###-#### frank...GAS ONLY
|
Mec-Aging Inspection | 2/13/2014 | 2/13/2014 | 2/14/2014 | | PEND |
Dixie Fellows
|
|
|
i rescheduled this for pm
|
Pressure Test | 11/13/2013 | 11/14/2013 | 11/14/2013 | A | PASS |
Dixie Fellows
|
|
|
###-####...20lb u/g to fire-pit ok
|
Pressure Test | 11/13/2013 | 11/13/2013 | 11/13/2013 | P | NH |
Dixie Fellows
|
|
|
Pressure test gas line to fire pit. Phone #: ###-#### >> Inspection requested via web by Frank Marturello...ACCESS TO HOUSE BLOCKED..I RESCHEDULED THIS FOR THURS AM
|
Mec-Aging Inspection | 11/7/2013 | 11/7/2013 | 11/12/2013 | | PASS |
Dixie Fellows
|
|
|
wip
|
Mec-Aging Inspection | 8/7/2013 | 8/7/2013 | 8/7/2013 | | PASS |
Dixie Fellows
|
|
|
wip
|
Rough-in | 5/3/2013 | 5/3/2013 | 5/3/2013 | P | PASS |
Troy James
|
|
|
Previous corrections by Bill was verified by Dave Hannah for rough approval. Duct blast passed and ducts in garage insulated.
|
Rough-in | 4/10/2013 | 4/10/2013 | 4/10/2013 | P | PART |
Bill VanDegrift
|
|
|
Doug: ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello ok to cover everything except the main supply trunk in the garage ceiling, 1-60# and 2-20# tests ok no duct test yet
|
Rough-in | 4/2/2013 | 4/2/2013 | 4/3/2013 | P | FAIL |
Bill VanDegrift
|
|
|
Rough In & Pressure Test. Thanks! Phone #: ###-#### >> Inspection requested via web by Frank Marturello 1) 1" clearance required at the B-Vent from water heater in garage ceiling and at wall above. 2)verify protection at B-Vent in 2nd floor wall. 3)dryer vent is disconnected at roof -support required. 4)insulate supply trunk in garage ceiling 5) 1-60# and 2-20# gas tests ok
|
Pressure Test | 4/3/2013 | 4/3/2013 | 4/3/2013 | A | PASS |
Bill VanDegrift
|
|
|
Rough In & Pressure Test. Thanks! Phone #: ###-#### >> Inspection requested via web by Frank Marturello 1-60# test and 2-20# tests ok
|
Rough-in | 3/29/2013 | 3/29/2013 | 3/29/2013 | P | NR |
Dixie Fellows
|
|
|
Doug: ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello...no manual j on site
|
Pressure Test | 3/29/2013 | 3/29/2013 | 3/29/2013 | P | NR |
Dixie Fellows
|
|
|
Doug: ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello
|
Pressure Test | 10/11/2012 | 10/11/2012 | 10/11/2012 | P | PART |
Dixie Fellows
|
|
|
Inspection and cover for fireplace, gas line pressure test. Phone #: ###-#### >> Inspection requested via web by Frank Marturello..20lb gas from outside masonry chimey to inside box ok...this was done before chimney was covered outside
|