Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberMEC13-02155
StatusFinaled
Name BUTLER HEATING
Site Address 5321 W EMERALD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Mechanical Permit - Alteration: Run gas piping to 12 dryers & 3 water heaters. Venting for 12 dryers and 3 water heaters. Make up air as per plans.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/20/20143/21/20143/21/2014APASS
DetailsChad Schwendiman
Phone #: ###-#### >> Inspection requested via web by Lori Dille
Final6/5/20136/6/20136/6/2013ANR
DetailsAlan Hauser
Pressure Test6/5/20136/5/20136/5/2013PPASS
DetailsAlan Hauser
1-60# and 3-20# test ok
Pressure Test6/3/20136/5/20136/5/2013AFAIL
DetailsAlan Hauser
the drawings show 2" pipe running down west side, but if using medium pressure 2# system then we need a 60# test