Final | 7/24/2014 | 7/24/2014 | 7/24/2014 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: 2088609415 >> Inspection requested via mobile web by Christian
|
Final | 7/23/2014 | 7/24/2014 | 7/24/2014 | A | CANC |
Chad Schwendiman
|
|
|
Phone #: 8609415 >> Inspection requested via mobile web by Christian Inspection cancelled via mobile web on Thursday, July 24, 2014.
|
Pressure Test | 7/21/2014 | 7/21/2014 | 7/21/2014 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: 8609415 >> Inspection requested via mobile web by Christian - 20LB GAS PRESSURE PASS
|
Final | 7/16/2014 | 7/17/2014 | 7/17/2014 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: 2088609415 >> Inspection requested via mobile web by Christian - NEED TO VENT POOL HEATER PER MANUFACTURES INSTRUCTIONS, NEED TO INSTALL UPER COMBUSTION AIR 12" BELOW CEILING, NEED 30" SERVICE CLEARANCE IN FRONT OF POOL HEATER, NEED TO SECURE POOL HEATER TO FLOOR PER MANUFACTURES INSTRUCTIONS.
|
Pressure Test | 7/16/2014 | 7/17/2014 | 7/17/2014 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: 2088609415 >> Inspection requested via mobile web by Christian - Gas pipe under sized
|
Rough-in | 5/1/2014 | 5/2/2014 | 5/2/2014 | A | PASS |
Chad Schwendiman
|
|
|
Call prior to going Phone #: 2088609415 >> Inspection requested via mobile web by Christian
|
Rough-in | 4/23/2014 | 4/24/2014 | 4/24/2014 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: 2088609415 >> Inspection requested via mobile web by Christian sanford - One of the fans is not vented yet. The flex duct is not installed per manufactors instructions. It needs to be installed, supported, & the ends fastened per the manufactors instructions. Heater vent has not been roughed in yet. Whats the plans for the heater vent?
|