Final | 8/29/2014 | 8/29/2014 | 8/29/2014 | P | PASS |
Eric Strole
|
|
|
Late afternoon inspection please. Phone #: ###-#### Inspection requested via web by Debbie Marino
|
Final | 8/28/2014 | 8/29/2014 | 8/29/2014 | A | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino-2nd test required on air balance report, rooms need to be with-in 20 percent of design cfm.
|
Pressure Test | 6/3/2014 | 6/4/2014 | 6/4/2014 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Debbie Marino - 20LB GAS PRESSURE PASS, 5LB FLUE PRESSURE PASS
|
Rough-in | 6/3/2014 | 6/4/2014 | 6/4/2014 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Debbie Marino
|
Pressure Test | 5/27/2014 | 5/28/2014 | 5/28/2014 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Debbie Marino - FAILED 5LB FLUE PRESSURE TEST. 20LB GAS PRESSURE PASS
|
Rough-in | 5/27/2014 | 5/28/2014 | 5/28/2014 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Debbie Marino - FRESH AIR INTAKE NEEDS TO BE 10' AWAY FROM EXHAUST.
|