Final | 8/19/2014 | 8/19/2014 | 8/19/2014 | P | PASS |
Chad Schwendiman
|
|
|
If the house is locked the garage code is 6949 Phone #: ###-#### >> Inspection requested via web by Krista Boss
|
Final | 7/25/2014 | 7/28/2014 | 7/28/2014 | A | FAIL |
Chad Schwendiman
|
|
|
garage code is 6949 Phone #: ###-#### >> Inspection requested via web by Krista Boss - can't find air balance report on site.
|
Rough-in | 5/27/2014 | 5/28/2014 | 5/28/2014 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss
|
Pressure Test | 5/27/2014 | 5/28/2014 | 5/28/2014 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss - 20LB GAS PRESSURE PASS, 5LB FLUE PRESSURE PASS.
|
Rough-in | 5/23/2014 | 5/27/2014 | 5/27/2014 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss - need to relocate attic access, it is blocked by duct work. Fresh air duct is not the correct size, needs to be 6". need to complete b-vent for water heater, need 1" clearance between insulation shield & b-vent, need 1" clearance to combustable from b-vent. need to pressure test pvc flue.
|
Pressure Test | 5/23/2014 | 5/27/2014 | 5/27/2014 | A | NR |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss
|
Rough-in | 5/27/2014 | 5/28/2014 | 5/27/2014 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss Inspection cancelled from web by: Krista Boss
|