Final | 12/9/2014 | 12/10/2014 | 12/10/2014 | A | PASS |
Bill VanDegrift
|
|
|
Re-inspection of the Final. Matt: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello final ok
|
Conference | 12/8/2014 | 12/9/2014 | 12/9/2014 | A | PASS |
Dixie Fellows
|
|
|
Re-inspection of the Final, conference with Shaun Vogler between 8:30 and 9:00 am. Phone #: ###-#### >> Inspection requested via web by Frank Marturello..discussed comb air
|
Final | 12/4/2014 | 12/8/2014 | 12/8/2014 | P | NR |
Dixie Fellows
|
|
|
Matt: ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello..need comb air door installed in w/h enclosure..need 2 disengaged foundation vents for comb air at furnace/wh...air balance reports o
|
Pressure Test | 10/23/2014 | 10/24/2014 | 10/24/2014 | A | PASS |
Troy James
|
|
|
Pressure Test additional underground gas line. Phone #: ###-#### >> Inspection requested via web by Frank Marturello gas piping to driveway ok 20# test
|
Pressure Test | 9/18/2014 | 9/18/2014 | 9/18/2014 | P | PASS |
Bill VanDegrift
|
|
|
Shaun: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello 1-60# and 1-20# gas test ok
|
Pressure Test | 9/17/2014 | 9/18/2014 | 9/18/2014 | A | FAIL |
Dixie Fellows
|
|
|
Please call Shaun so he can explain why we need another Pressure Test. ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello
|
Rough-in | 7/10/2014 | 7/10/2014 | 7/10/2014 | P | PASS |
Dixie Fellows
|
|
|
Re-inspection of the rough in. Shaun: ###-#### or Matt: ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello
|
Rough-in | 7/8/2014 | 7/9/2014 | 7/9/2014 | A | FAIL |
Eric Strole
|
|
|
Re-inspection of the Rough In. Contact Shaun: ###-#### or Matt: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello-Missing supply in guest bath and missing transfer grills basement bedrooms. Return main level is not per manual-j but is ok and will be changed on manual-j by final.
|
Rough-in | 7/3/2014 | 7/7/2014 | 7/7/2014 | A | FAIL |
Chad Schwendiman
|
|
|
Crawl not complete. reschedule when done.
|
Pressure Test | 7/3/2014 | 7/3/2014 | 7/3/2014 | P | PASS |
Eric Strole
|
|
|
Contact Shaun: ###-#### or Matt: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello-20 & 60 lb gas test pass
|
Rough-in | 7/3/2014 | 7/3/2014 | 7/3/2014 | P | FAIL |
Eric Strole
|
|
|
Contact Shaun: ###-#### or Matt: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello-Need approved manual-j on site
|