Permit Information
Permit NumberMEC14-02877
StatusFinaled
Name ARCTIC AIR INC
Site Address 740 W SANTA PAULA PL
Project Name 
Customer Number 
ePlanReviewNo
Description
Mechanical Permit - Alteration: Install new ductwork and hvac equipment and gas lines
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/23/201410/24/201410/24/2014APASS
DetailsBill VanDegrift
Final mechanical w/ fireplace Phone #: ###-#### Inspection requested via web by Konrad Swartz final ok
Final10/2/201410/3/201410/3/2014AFAIL
DetailsChad Schwendiman
453--9272 - need to vent water heater, need to air balance, need to complete range hood
Pressure Test10/3/201410/3/201410/3/2014APASS
DetailsChad Schwendiman
453--9272 - Duct blast pass
Rough-in7/21/20147/22/20147/22/2014APASS
DetailsChad Schwendiman
Reinspect Phone #: ###-#### >> Inspection requested via web by Konrad Swartz
Pressure Test7/22/20147/22/20147/22/2014APASS
DetailsChad Schwendiman
Reinspect Phone #: ###-#### >> Inspection requested via web by Konrad Swartz - 20LB GAS PRESSURE PASS.
Pressure Test7/17/20147/17/20147/17/2014PFAIL
DetailsChad Schwendiman
Re inspect Phone #: ###-#### >> Inspection requested via web by Konrad Swartz -20LB GAS PRESSURE FAIL TO WATER HEATER. 5LB FLUE PRESSURE PASS
Rough-in7/17/20147/17/20147/17/2014PFAIL
DetailsChad Schwendiman
Re inspect Phone #: ###-#### >> Inspection requested via web by Konrad Swartz - NEED 6' FRESH AIR TO RETURN PLENUM
Pressure Test7/11/20147/11/20147/11/2014PFAIL
DetailsChad Schwendiman
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz - NEED TO DO A 5LB PRESSURE TEST ON PVC FLUE.
Rough-in7/11/20147/11/20147/11/2014PFAIL
DetailsChad Schwendiman
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz - NEED APPROVED MANUAL J ON SITE, NEED TO ATTACH MEC PERMIT TO BLD PERMIT.