Final | 10/8/2014 | 10/9/2014 | 10/9/2014 | P | PASS |
Chad Schwendiman
|
|
|
Jason w/TML, please call before going, thank you! Phone #: ###-#### Inspection requested via web by Michele LaMott
|
Final | 10/8/2014 | 10/8/2014 | 10/8/2014 | P | NR |
Chad Schwendiman
|
|
|
Jason w/TML Phone #: ###-#### Inspection requested via web by Michele LaMott
|
Final | 10/7/2014 | 10/8/2014 | 10/8/2014 | A | FAIL |
Chad Schwendiman
|
|
|
Jason w/TML Phone #: ###-#### Inspection requested via web by Michele LaMott - need to pipe secondary condensate drain on coil or install a wet switch, water leaking out of duct work at humidifier location, steam hose is trapped.
|
Final | 9/25/2014 | 10/1/2014 | 10/1/2014 | P | CANC |
Chad Schwendiman
|
|
|
Jason w/TML, please call b4 going, thank you! Happy Birthday last week :D Phone #: ###-#### >> Inspection requested via web by Michele LaMott Inspection cancelled from web by: Michele LaMott
|
Rough-in | 8/7/2014 | 8/11/2014 | 8/11/2014 | A | PASS |
Dixie Fellows
|
|
|
Dusty w/TML Phone #: ###-#### >> Inspection requested via web by Michele LaMott..supply duct in attic ok
|
Rough-in | 7/24/2014 | 7/25/2014 | 7/25/2014 | A | FAIL |
Chad Schwendiman
|
|
|
Micah w/TML, balance damper & ductwork Phone #: ###-#### >> Inspection requested via web by Michele LaMott - 2ND FLOOR LOFT SUPPLY DUCT RUN TO SMALL. IT'S 6" AND NEEDS TO BE 9".
|
Pressure Test | 7/21/2014 | 7/22/2014 | 7/22/2014 | A | PASS |
Bill VanDegrift
|
|
|
20# test ok
|
Rough-in | 7/21/2014 | 7/21/2014 | 7/21/2014 | P | NR |
Bill VanDegrift
|
|
|
Micah w/TML, inspect ductwork only Phone #: ###-#### Inspection requested via web by Michele LaMott need ACCA report, gas piping in floor needs to be sleeved.
|