Rough-in | 8/26/2015 | 8/27/2015 | 8/27/2015 | A | PASS |
Chad Schwendiman
|
|
|
Tower 4 and 2nd Floor Final Phone #: ###-#### Inspection requested via web by Shelia Gibson
|
Final | 8/27/2015 | 8/27/2015 | 8/27/2015 | A | PASS |
Chad Schwendiman
|
|
|
Tower 4 and 2nd Floor Final Phone #: ###-#### Inspection requested via web by Shelia Gibson
|
Rough-in | 8/25/2015 | 8/26/2015 | 8/26/2015 | A | PASS |
Chad Schwendiman
|
|
|
Tower 4, 3rd, 4th and 5th Floors - Final Phone #: ###-#### Inspection requested via web by Shelia Gibson - 3rd, 4th, and 5th floors pass
|
Final | 8/12/2015 | 8/13/2015 | 8/13/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 3 final for the rooms, and Tower 4 corridors all floors Phone #: ###-#### Inspection requested via web by Shelia Gibson - tower 3 okay,
|
Rough-in | 7/27/2015 | 7/27/2015 | 7/27/2015 | P | PASS |
Troy James
|
|
|
Fitness final Phone #: ###-#### >> Inspection requested via web by Shelia Gibson ok to cover fitness area with restrooms
|
Rough-in | 7/17/2015 | 7/17/2015 | 7/17/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 4 Elevator Lobbys Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover hard lids
|
Rough-in | 7/9/2015 | 7/10/2015 | 7/10/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 2 final Phone #: ###-#### Inspection requested via web by Shelia Gibson - temporary occupancy for tower 2 okay.
|
Rough-in | 7/8/2015 | 7/8/2015 | 7/8/2015 | P | PART |
Chad Schwendiman
|
|
|
Garage Units Phone #: ###-#### Inspection requested via web by Shelia Gibson - garage units okay
|
Rough-in | 7/1/2015 | 7/2/2015 | 7/2/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 1 Final Phone #: ###-#### Inspection requested via web by Shelia Gibson - tower 1 temporary occupancy okay
|
Rough-in | 6/30/2015 | 7/1/2015 | 7/1/2015 | A | FAIL |
Chad Schwendiman
|
|
|
Tower 1 and Tower 2 Final Phone #: ###-#### Inspection requested via web by Shelia Gibson - need to complete the condensates on the units in the rooms
|
Rough-in | 6/29/2015 | 6/30/2015 | 6/30/2015 | A | PART |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Shelia Gibson - 2nd floor tower 4 okay to cover
|
Rough-in | 6/23/2015 | 6/24/2015 | 6/24/2015 | A | PASS |
Troy James
|
|
|
Lobby Cover Phone #: ###-#### >> Inspection requested via web by Shelia Gibson ok to cover ceiling in lobby area
|
Rough-in | 6/22/2015 | 6/22/2015 | 6/22/2015 | P | PASS |
Troy James
|
|
|
Tower 4 Shaft Cover Phone #: ###-#### >> Inspection requested via web by Shelia Gibson ok to cover tower 4 shaft, rtu 2a and 2c
|
Rough-in | 6/16/2015 | 6/17/2015 | 6/17/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 4 Shaft Tower 4 2nd floor cover-up Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to insulate duct
|
Rough-in | 6/10/2015 | 6/10/2015 | 6/10/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 4 3rd floor Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover
|
Rough-in | 6/8/2015 | 6/9/2015 | 6/9/2015 | A | PART |
Chad Schwendiman
|
|
|
tower 4 4th floor cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover
|
Rough-in | 6/4/2015 | 6/5/2015 | 6/5/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 4 5th floor cover Phone #: ###-#### Inspection requested via web by Shelia - okay to cover soffits and hard lids
|
Rough-in | 6/3/2015 | 6/4/2015 | 6/4/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 4 3rd floor duct Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to insulate duct work
|
Rough-in | 6/3/2015 | 6/3/2015 | 6/3/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 1 Shaft all floors Phone #: ###-#### Inspection requested via web by Shelia Gibson - Okay to revover the shaft in tower 1
|
Rough-in | 6/1/2015 | 6/2/2015 | 6/2/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 3 3rd and 2nd floors pods cover Tower 4 5th and 4th floors elevator lobbys Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover
|
Rough-in | 5/27/2015 | 5/28/2015 | 5/28/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 4 4th floor cover Lobby cover Tower 3 5th floor pods commons cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover lobby, okay to cover 5th floor tower 3, okay to insulate duct 4th floor tower 4
|
Rough-in | 5/26/2015 | 5/26/2015 | 5/26/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 3 2nd floor first 6 rooms cover Tower 3 5th and 4th floor pods cover commons cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover soffits and hard lids 2nd floor tower 3 first 6 rooms. okay t cover soffits and hard lids 4th floor tower 3 pods.
|
Rough-in | 5/21/2015 | 5/22/2015 | 5/22/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 3 5th; 4th floor pods Tower 2 3rd floor corridor cover Tower 3 2nd floor 1st 6 rooms cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to insulate duct in tower 2. Need to reinspect tower 3 after sheetrock is removed and access doors are relocted in romms 210, 212, & 213
|
Rough-in | 5/20/2015 | 5/21/2015 | 5/21/2015 | A | PART |
Chad Schwendiman
|
|
|
5th Floor Tower 4 insulation 4th,3rd and 2nd floor tower 4 insulation corridor Phone #: ###-#### Inspection requested via web by Shelia Gibson - duct seal okay to insulate
|
Rough-in | 5/15/2015 | 5/15/2015 | 5/15/2015 | P | CANC |
Chad Schwendiman
|
|
|
2nd Floor Bathroom for Cover Phone #: ###-#### >> Inspection requested via web by Shelia Gibson Inspection cancelled from web by: Shelia Gibson
|
Rough-in | 5/8/2015 | 5/11/2015 | 5/11/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 3 3rd floor first 6 rooms cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover soffits and hard lids
|
Rough-in | 5/7/2015 | 5/7/2015 | 5/7/2015 | P | PART |
Chad Schwendiman
|
|
|
Fitness and common areas Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to insulate ductwork
|
Rough-in | 5/4/2015 | 5/5/2015 | 5/5/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 3 4th floor first 6 rooms cover up Tower 3 2nd floor pods insulate cover up lobby linear grilles tower 4 5th floor corridor insulate cove Phone #: ###-#### Inspection requested via web by Shelia Gibson okay to cover soffits in lobby, okay to insulate duct work on 2nf loor tower 3, okay to cover soffits and hard lids 4th floor tower 3
|
Rough-in | 5/4/2015 | 5/5/2015 | 5/4/2015 | A | CANC |
Chad Schwendiman
|
|
|
Tower 3 4th floor first 6 rooms cover up Tower 3 2nd floor pods insulate cover up lobby linear grilles tower 4 5th floor corridor insulate cover Phone #: ###-#### >> Inspection requested via web by Shelia Gibson Inspection cancelled from web by: Shelia Gibson
|
Rough-in | 4/30/2015 | 5/1/2015 | 5/1/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 3 5th floor first 6 rooms Lobby shaft duct Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover soffits and hard lids
|
Rough-in | 4/29/2015 | 4/30/2015 | 4/30/2015 | P | PART |
Chad Schwendiman
|
|
|
LOBBY COVER Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to insulate duct work, okay to cover shaft at stair tower 1
|
Rough-in | 4/29/2015 | 4/29/2015 | 4/29/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 3 3rd Floor Pods Phone #: ###-#### Inspection requested via web by Shelia Gibson - duct seal okay
|
Rough-in | 4/27/2015 | 4/28/2015 | 4/28/2015 | A | PART |
Chad Schwendiman
|
|
|
RTU 4 COVER Phone #: ###-#### Inspection requested via web by Shelia Gibson - duct work in chase in the lobby okay.
|
Rough-in | 4/23/2015 | 4/24/2015 | 4/24/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 2 2nd floor cover up RTU 4 cover up Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover soffits and hrd lids in tower 2 2nd floor. okay to insulate duct in saft of stair tower 1
|
Rough-in | 4/20/2015 | 4/21/2015 | 4/21/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 3 2nd floor first 6 rooms Tower 3 5th floor pods Phone #: ###-#### Inspection requested via web by Shelia Gibson - duct seal okay, Smoke fire dampers through roof line into corridoor okay on 5th floor tower 1
|
Rough-in | 4/15/2015 | 4/15/2015 | 4/15/2015 | P | PART |
Chad Schwendiman
|
|
|
RTU 5 Cover Tower 2 Corridor 5th and 4th floors Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover
|
Rough-in | 4/13/2015 | 4/14/2015 | 4/14/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 3 3rd floor 4 bedroom rooms Tower 3 5th floor first 6 bedrooms Lobby area just rooms Phone #: ###-#### Inspection requested via web by Shelia Gibson - duct seal pass, okay to insulate
|
Rough-in | 4/9/2015 | 4/10/2015 | 4/10/2015 | P | PART |
Chad Schwendiman
|
|
|
Late Afternoon Please Tower 2 3rd floor cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover soffits
|
Rough-in | 4/7/2015 | 4/8/2015 | 4/8/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 1 shaft cover Tower 2 2nd floor east side Tower 3 3rd floor the 4 2 bedrooms Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to insulate ducts, shaft duct okay
|
Rough-in | 4/6/2015 | 4/6/2015 | 4/6/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 2 4th Floor cover soffit Tower 3 4th floor insulate duct work 1st 6 rooms Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover soffits on 4th floor of tower 2, okay to insulate duct 4th floor tower 3
|
Rough-in | 4/3/2015 | 4/3/2015 | 4/3/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 1 shaft cover up Phone #: ###-#### Inspection requested via web by Shelia Gibson - tower 1 shaft okay
|
Rough-in | 4/1/2015 | 4/1/2015 | 4/1/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 2 2nd Floor Duct Work excepted 218 Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to insulate units 224, 225, 226, 228
|
Rough-in | 3/30/2015 | 3/31/2015 | 3/31/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 4- 3,2,4 floor cover-up Tower 1- 5,4 floor corridors Tower 2- 5 floor soffits cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover bottom of tgi's and walls tower 4, Okay to cover soffits in tower 2 5th floor except for room 518. Okay to cover corridoor ceiling 4th, 5th, floors of tower 1.
|
Rough-in | 3/26/2015 | 3/27/2015 | 3/27/2015 | P | PART |
Chad Schwendiman
|
|
|
RTU 5 Shaft on 5th, 4th and 3rd Floors Tower 2 corridors on 5th and 4th Floors Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to frame in shaft walls on 3rd. through 5th floors tower2
|
Rough-in | 3/24/2015 | 3/25/2015 | 3/25/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 3 floors 4,3 and 2 pods Phone #: ###-#### Inspection requested via web by Shelia Gibson - 2nd, 3rd, and 4th floors tower pods okay to cover bottom of tgi's and walls.
|
Rough-in | 3/23/2015 | 3/24/2015 | 3/24/2015 | P | NR |
Chad Schwendiman
|
|
|
Tower 3 pods 4,3 and 2 floors Phone #: ###-#### Inspection requested via web by Shelia Gibson - Not ready on tower 3. 5 floor tower 4 okay to cover bottom of tgi's and walls
|
Rough-in | 3/18/2015 | 3/19/2015 | 3/19/2015 | P | PART |
Chad Schwendiman
|
|
|
TOWER 2 RM 423 AND 3RD FLOOR, TOWER 3 patio soffit Phone #: ###-#### Inspection requested via web by Shelia Gibson - duct seal okay in rm 423, 3rd floor tower 2. Patio soffits okay on 2nd floor tower 3.
|
Rough-in | 3/16/2015 | 3/17/2015 | 3/17/2015 | A | PART |
Chad Schwendiman
|
|
|
TOWER 2 FLOOR, 3RD, 4TH AND 5TH Phone #: ###-#### Inspection requested via web by Shelia Gibson - Duct okay to insulate tower 2 4th, and 5th floors, and west half of 3rd floor
|
Rough-in | 3/13/2015 | 3/16/2015 | 3/16/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 1 2nd Floor Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover soffits, & bathroom ceilings in tower 1 2nd floor
|
Rough-in | 3/11/2015 | 3/11/2015 | 3/11/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 3 floor 4th,3rd and 2nd Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover bottom of tgi's except for the pod units.
|
Rough-in | 3/6/2015 | 3/6/2015 | 3/6/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 3 3rd and 4th Floor Patio''s Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover patio ceilings
|
Rough-in | 3/4/2015 | 3/5/2015 | 3/5/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 1 5th floor shaft work Phone #: ###-#### Inspection requested via web by Shelia Gibson - 5th floor tower 1 shaft okay to cover.
|
Rough-in | 3/4/2015 | 3/4/2015 | 3/4/2015 | P | PART |
Chad Schwendiman
|
|
|
5th floor tower 3 Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover bottom of trusses on 5th floor tower 3.
|
Rough-in | 3/2/2015 | 3/3/2015 | 3/3/2015 | A | PART |
Chad Schwendiman
|
|
|
2nd floor Tower 1 ductwork for cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to insulate duct work 2nd. floor tower 1
|
Rough-in | 2/25/2015 | 2/26/2015 | 2/26/2015 | A | PART |
Chad Schwendiman
|
|
|
Tower 1 3rd Floor cover Room 518 Cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover soffits on 3rd floor tower 1, 518 okay to cover.
|
Conference | 2/23/2015 | 2/23/2015 | 2/23/2015 | P | DONE |
Chad Schwendiman
|
|
|
|
Rough-in | 2/13/2015 | 2/13/2015 | 2/13/2015 | P | PART |
Chad Schwendiman
|
|
|
TOWER TWO Phone #: ###-#### Inspection requested via web by Shelia Gibson - tower 2 2nd. through 5th floors ok to cover bottomg of tgi's except for room #518
|
Rough-in | 2/12/2015 | 2/13/2015 | 2/13/2015 | A | PART |
Chad Schwendiman
|
|
|
3rd. floor tower 1 Mike ###-#### - 3rd and 2nd floor tower 1 okay to cover bottom of tgi's and patch around fire dampers. tower 2 10 x 8 fire dampers in the kitchens are still installed wrong. need to install per manufactures instructions.
|
Rough-in | 2/12/2015 | 2/12/2015 | 2/13/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 1 4th floor and tower 2 4th floor Phone #: ###-#### Inspection requested via web by Shelia Gibson - 4th floor tower 1 okay to patch around fire dampers
|
Rough-in | 2/10/2015 | 2/11/2015 | 2/11/2015 | A | FAIL |
Chad Schwendiman
|
|
|
Tower 2 3rd ; 2nd floor Phone #: ###-#### Inspection requested via web by Shelia Gibson - need to move dryer duct into walls wehre they penetrate the ceiling
|
Rough-in | 2/5/2015 | 2/6/2015 | 2/6/2015 | A | PART |
Chad Schwendiman
|
|
|
TOWER 1 4TH FLOOR TOWER 2 3RD AND 2ND Phone #: ###-#### Inspection requested via web by Shelia Gibson - 2nd. and 3rd floors of tower 2 okay to cover bottom of tgi's all units
|
Conference | 2/6/2015 | 2/6/2015 | 2/6/2015 | A | FAIL |
Chad Schwendiman
|
|
|
The ceiling radiation dampers are not installed per the manufactures instructions on the 2nd. through 5th. floors of tower 1, and 4th and 5th. floors of tower 2. Need to install per manufactures instructions or get the manufactures approval for the way they have been installed
|
Rough-in | 2/5/2015 | 2/5/2015 | 2/5/2015 | P | PART |
Chad Schwendiman
|
|
|
Tower 2 Phone #: ###-#### Inspection requested via web by Shelia Gibson - patio ceilings okay to cover on all of tower #2
|
Rough-in | 2/2/2015 | 2/3/2015 | 2/3/2015 | A | PEND |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Shelia Gibson - This was a confrence to discuss the ceiling dampers. They are not currently installed per the manufactures instructions. Need to get manufacture to approve the insallation or install them per the instructions
|
Rough-in | 2/2/2015 | 2/2/2015 | 2/2/2015 | P | NR |
Chad Schwendiman
|
|
|
Tower 2 Soffit Phone #: ###-#### Inspection requested via web by Shelia Gibson
|
Conference | 2/2/2015 | 2/2/2015 | 2/2/2015 | P | DONE |
Chad Schwendiman
|
|
|
Meet with Jim - need the installation instructions for the ceiling fire dampers
|
Rough-in | 1/30/2015 | 1/30/2015 | 1/30/2015 | P | PART |
Chad Schwendiman
|
|
|
5th Floor Tower 1 Phone #: ###-#### Inspection requested via web by Shelia Gibson - 5th floor tower 1 okay to cover soffits except for room number 530.
|
Rough-in | 1/28/2015 | 1/29/2015 | 1/29/2015 | A | PART |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Shelia Gibson - tower 2, north west pods okay to cover patio ceilings 2nd. thru 5th. floors
|
Rough-in | 1/27/2015 | 1/28/2015 | 1/28/2015 | A | PART |
Eric Strole
|
|
|
Tower 2 4th floor cover Phone #: ###-#### Inspection requested via web by Shelia Gibson-Tower 2 4th flr ok to cover lids in units only.
|
Rough-in | 1/26/2015 | 1/26/2015 | 1/26/2015 | P | PART |
Chad Schwendiman
|
|
|
5TH FLOOR TOWER 2 Phone #: ###-#### Inspection requested via web by Shelia Gibson - 5th. floor tower 2 okay to cover bottom of joist in the units only. do not cover the patio ceilings work is not complete.
|
Rough-in | 12/22/2014 | 12/23/2014 | 12/23/2014 | A | PART |
Chad Schwendiman
|
|
|
tower one level two cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - okay to cover ceilings 2nd. level tower 1
|
Rough-in | 12/15/2014 | 12/16/2014 | 12/16/2014 | A | PART |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Shelia Gibson - 3rd, and 4th. floors tower 1 okay to cover ceilings.
|
Rough-in | 12/2/2014 | 12/2/2014 | 12/2/2014 | P | PART |
Chad Schwendiman
|
|
|
5th floor line sets for cover Phone #: ###-#### Inspection requested via web by Shelia Gibson - 5th. floor tower 1 ceilings and walls okay to cover
|
Rough-in | 11/21/2014 | 11/24/2014 | 11/24/2014 | A | PART |
Chad Schwendiman
|
|
|
5TH FLOOR EXHAUST APPROVED FOR COVER UP Phone #: ###-#### Inspection requested via web by Shelia Gibson - Tower 1, 5th floor bath exhaust and dryer vents running in trusses okay
|
Conference | 11/21/2014 | 11/21/2014 | 11/21/2014 | A | CANC |
Chad Schwendiman
|
|
|
Meeting on dryer vents. 9:00. this was cancel
|
Rough-in | 11/20/2014 | 11/20/2014 | 11/20/2014 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Shelia Gibson - this was a confrence regardding dryer ducts.
|