Permit Information
Permit NumberMEC14-05180
StatusFinaled
Name WESTERN HEATING & A/C
Site Address 204 N CAPITOL BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Mechanical Permit - New: RETROFIT SPIRAL PIPE & RELOCATE CUSTOMERS FURNACE
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/2/20159/2/20159/2/2015PPASS
DetailsDixie Fellows
please call Zac ###-#### >> Inspection requested via web by Dustin Rich..NO CARD ON SITE
Conference1/7/20151/7/20151/7/2015PDONE
DetailsTroy James
Met with Richard Katchner and Chris the general to discuss the return air in basement and the bread oven at main level. Engineer is to provide drawing of return ducting into kitchen and in the office. Also to provide letter stating the bread oven is ok without hood.
Final1/5/20151/6/20151/6/2015AFAIL
DetailsTroy James
Phone #: ###-#### Inspection requested via web by Dustin Rich
The return plenum duct to the guru donuts cannot terminate above ceiling and be an open plenum. Need to duct return to kitchen and office area.
The bread oven is not shown on the plans. The engineer needs to address how the heat from the oven is to be removed from the space.
Rough-in12/3/201412/3/201412/3/2014PFAIL
DetailsTroy James
The chase built to continue to the first floor is required to be built as a rated shaft design per the mechanical plans.
The return air at the basement cannot terminate as above ceiling and create a plenum. Must be ducted to the kitchen area. Called the mechanical engineer and informed him of these issues that are going to need to be addressed.
Rough-in12/1/201412/2/201412/2/2014APASS
DetailsTroy James
installer Tom ###-#### Phone #: ###-#### Inspection requested via web by Dustin Rich
ok spiral duct only