Permit Information
Permit NumberMEC14-05708
StatusFinaled
Name COX MECHANICAL INC
Site Address 3300 S SHOSHONE ST
Project NameBoise Fairfield Inn Property I
Customer Number890-4261
ePlanReviewNo
Description
Mechanical Permit - Alteration: HVAC per plans to include relocate exhaust fan, new exhaust fan on second floor, 2 each Daikin heat pumps with 3each fan coild
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/24/20152/25/20152/25/2015APASS
DetailsAlan Hauser
Final2/4/20152/4/20152/4/2015PNR
DetailsBill VanDegrift
Phone #: ###-#### Inspection requested via web by Robin Cox imc 607.4 label damper in kitchen ceiling. verify existing exhaust fans have radiation dampers.
Rough-in1/27/20151/28/20151/28/2015APASS
DetailsBill VanDegrift
cover guest laundry, second floor. 1ea FSD , fan with fire damper Phone #: ###-#### Inspection requested via web by Robin Cox dampers and ducts in the 2nd floor laundry ok
Conference1/2/20151/2/20151/2/2015ADONE
DetailsChad Schwendiman
ex Phone #: ###-#### Inspection requested via web by Robin Cox - Discussed routing of exhuast for laundry room on 2nd floor. Noticed that the exhaust fans on the 1st. and 2nd floors are being installed in between the tgi"s, this is a fire rated assembelly and will need fire dampers installed at fire asseembelly penetration. The city plans also show a transfer above door on on 2nd. flioor laundry room. This has a smoke damper on it, It looks like when installed it will also penetrate inside the tgi"s of the laundry room which will require protection of the assembelly where it is penetrated in the ceiling of the laundry room for the grill.