Final | 2/24/2015 | 2/25/2015 | 2/25/2015 | A | PASS |
Alan Hauser
|
|
|
|
Final | 2/4/2015 | 2/4/2015 | 2/4/2015 | P | NR |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Robin Cox imc 607.4 label damper in kitchen ceiling. verify existing exhaust fans have radiation dampers.
|
Rough-in | 1/27/2015 | 1/28/2015 | 1/28/2015 | A | PASS |
Bill VanDegrift
|
|
|
cover guest laundry, second floor. 1ea FSD , fan with fire damper Phone #: ###-#### Inspection requested via web by Robin Cox dampers and ducts in the 2nd floor laundry ok
|
Conference | 1/2/2015 | 1/2/2015 | 1/2/2015 | A | DONE |
Chad Schwendiman
|
|
|
ex Phone #: ###-#### Inspection requested via web by Robin Cox - Discussed routing of exhuast for laundry room on 2nd floor. Noticed that the exhaust fans on the 1st. and 2nd floors are being installed in between the tgi"s, this is a fire rated assembelly and will need fire dampers installed at fire asseembelly penetration. The city plans also show a transfer above door on on 2nd. flioor laundry room. This has a smoke damper on it, It looks like when installed it will also penetrate inside the tgi"s of the laundry room which will require protection of the assembelly where it is penetrated in the ceiling of the laundry room for the grill.
|