Final | 5/7/2015 | 5/8/2015 | 5/8/2015 | A | PASS |
Chad Schwendiman
|
|
|
Dale Phone #: ###-####
|
Rough-in | 1/2/2015 | 1/5/2015 | 1/5/2015 | A | PASS |
Dixie Fellows
|
|
|
Dale Phone #: ###-####..r/i ok
|
Pressure Test | 12/31/2014 | 1/2/2015 | 1/2/2015 | A | PASS |
Chad Schwendiman
|
|
|
Dale Phone #: ###-#### - 5lb flue, 20lb gas pass
|
Rough-in | 12/31/2014 | 1/2/2015 | 1/2/2015 | A | FAIL |
Chad Schwendiman
|
|
|
Dale Phone #: ###-#### - Need approved acca report on site for rough in, need 1" gap between insulation shield and B-vent for water heater, need to seal floor boots to the floor
|