Final | 6/3/2015 | 6/3/2015 | 6/3/2015 | A | PASS |
Chad Schwendiman
|
|
|
Ready Phone #: ###-#### Inspection requested via web by Russ Curtis
|
Final | 6/2/2015 | 6/2/2015 | 6/3/2015 | P | FAIL |
Chad Schwendiman
|
|
|
Ready Phone #: ###-#### Inspection requested via web by Russ Curtis - no air balance report on site. rescheduled for 6-3 AM
|
Rough-in | 3/26/2015 | 3/27/2015 | 3/27/2015 | A | PASS |
Eric Strole
|
|
|
Ready after 10 am. Thank you Phone #: ###-#### Inspection requested via web by Russ Curtis-20 lb gas test and rough-in pass
|
Rough-in | 3/25/2015 | 3/26/2015 | 3/26/2015 | P | FAIL |
Chad Schwendiman
|
|
|
Ready for gas pressure and HVAC inspection after 12 pm please. Phone #: ###-#### Inspection requested via web by Russ Curtis - Need ceiling access in front of coil in the attic. it is currently unservicable, Need a 20lb test on a 30lb gauge for the gas piping, Can't penetrate the exterior soffit with condesate in a WUI zone, Need the complete approved acca report on site note just the cover page.
|