Permit Information
Permit NumberMEC15-03228
StatusFinaled
Name QUALITY HEATING & COOLING CO
Site Address 1726 S MANITOU AVE
Project Name 
Customer Number15192
ePlanReviewNo
Description
Alteration or Repair: gas furnace, ac & wh replacement
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/22/20173/23/20173/23/2017APASS
DetailsChad Schwendiman
Homeowner ###-####, Request flue pressure test witness ; final after 10 AM, contact Aaron (QHC) @ ###-#### or Kevin (QHC) @ Phone #: ###-#### Inspection requested via web by Kevin Pratley
Pressure Test3/22/20173/23/20173/23/2017APASS
DetailsChad Schwendiman
Homeowner ###-####, Request flue pressure test witness ; final after 10 AM, contact Aaron (QHC) @ ###-#### or Kevin (QHC) @ Phone #: ###-#### Inspection requested via web by Kevin Pratley - 5lb flue pass
Mec-Aging Inspection3/13/20173/13/20173/15/2017 NR
DetailsBill VanDegrift
talked to Kevin, he'll make sure corrections were made and get it called in for a final.
Mec-Aging Inspection12/12/201612/12/201612/12/2016 CANC
DetailsChad Schwendiman
Mec-Aging Inspection9/1/20169/1/20169/2/2016 PEND
DetailsChad Schwendiman
I called and spoke with Diane with Quality heating and cooling, she said she was going to get with kevin about this permit.
Mec-Aging Inspection6/2/20166/2/20166/2/2016 CANC
DetailsChad Schwendiman
Mec-Aging Inspection3/3/20163/3/20163/3/2016 CANC
DetailsChad Schwendiman
Final8/17/20158/20/20158/20/2015PCANC
DetailsChad Schwendiman
request late PM inspection, contact Jorday (QHC) @ ###-#### or Kevin @ Phone #: ###-#### >> Inspection requested via web by Kevin Pratley Inspection cancelled from web by: Kevin Pratley
Pressure Test8/17/20158/20/20158/20/2015PCANC
DetailsChad Schwendiman
request late PM inspection, contact Jorday (QHC) @ ###-#### or Kevin @ Phone #: ###-#### >> Inspection requested via web by Kevin Pratley Inspection cancelled from web by: Kevin Pratley
Final7/21/20157/21/20157/21/2015PFAIL
DetailsChad Schwendiman
contact Shane (QHC) @ ###-#### or Kevin (QHC) @ Phone #: ###-#### Inspection requested via web by Kevin - see corrections for pressure test
Pressure Test7/21/20157/21/20157/21/2015PFAIL
DetailsChad Schwendiman
contact Shane (QHC) @ ###-#### or Kevin (QHC) @ Phone #: ###-#### Inspection requested via web by Kevin Pratley - flue pressure fail, need 1" clearance to pvc flue from b-vent flue. need to install co sensors
Final7/10/20157/10/20157/10/2015PFAIL
DetailsChad Schwendiman
contact owner @ ###-#### or Shane (QHC) ###-#### or Kevin (QHC) @ Phone #: ###-#### Inspection requested via web by Kevin Pratley - Need to pressure test pvc flue, need to be able to verify 1" clearance between pvc and b-vent flues, need to install CO sensors