Final | 12/1/2015 | 12/1/2015 | 12/1/2015 | P | PASS |
Chad Schwendiman
|
|
|
|
Final | 11/30/2015 | 12/1/2015 | 12/1/2015 | A | FAIL |
Chad Schwendiman
|
|
|
James Phone #: ###-#### no access
|
Final | 11/19/2015 | 11/23/2015 | 11/23/2015 | A | FAIL |
Chad Schwendiman
|
|
|
JAMES Phone #: ###-#### - No air balance report on site, need to complete range vent, need to install solar bath fan vents
|
Rough-in | 9/4/2015 | 9/4/2015 | 9/4/2015 | P | PASS |
Chad Schwendiman
|
|
|
James Phone #: ###-####
|
Rough-in | 9/3/2015 | 9/4/2015 | 9/4/2015 | A | FAIL |
Chad Schwendiman
|
|
|
Paul Phone #: ###-#### 1) supply duct to master bath is under sized 2) Gas guage is under 20lbs 3) need to rough in line set for condensor 4) need to rough in bath fan vents
|
Rough-in | 9/3/2015 | 9/3/2015 | 9/3/2015 | P | FAIL |
Chad Schwendiman
|
|
|
Sooner the better // James Phone #: ###-#### - no approved manual J on site, Need to pressure test pvc flue, gas piping not complete
|