Final | 12/2/2015 | 12/3/2015 | 12/3/2015 | A | PASS |
Chad Schwendiman
|
|
|
Access #1234 Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Rough-in | 9/3/2015 | 9/4/2015 | 9/4/2015 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Pressure Test | 9/3/2015 | 9/3/2015 | 9/3/2015 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - 20lb gas, 5lb flue pass
|
Rough-in | 9/3/2015 | 9/3/2015 | 9/3/2015 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN Need approved manual J on site, need 1" clearance between insulation shield and b-vent, need to install fresh air to return plenum
|