Permit Information
Permit NumberMEC15-04560
StatusFinaled
Name KMD MECHANICAL
Site Address 5244 W OVERLAND RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: HVAC work
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/20/201511/20/201511/20/2015PPASS
DetailsChad Schwendiman
Final11/10/201511/10/201511/10/2015PPART
DetailsChad Schwendiman
Can you please have the inspector call me ###-#### Karl Thank You. Phone #: ###-#### Inspection requested via web by Karl Hestekin - still need economizer on rtu, exhaust in mens shower and detector testing complete
Final11/4/201511/5/201511/5/2015ANR
DetailsBill VanDegrift
Phone #: ###-#### Inspection requested via web by Karl Hestekin
1) needs an economizer on the new rtu.
2) need to verify the duct detectors on all the rtu's over 2000 cfm
3) need exhaust in the mens shower room.