Final | 6/20/2016 | 6/22/2016 | 6/22/2016 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss
|
Final | 6/20/2016 | 6/23/2016 | 6/20/2016 | A | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss Inspection cancelled from web by: Krista Boss
|
Mec-Aging Inspection | 4/25/2016 | 4/25/2016 | 4/25/2016 | | CANC |
Chad Schwendiman
|
|
|
WIP
|
Rough-in | 11/16/2015 | 11/16/2015 | 11/16/2015 | P | PASS |
Chad Schwendiman
|
|
|
Call Chuck ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
|
Pressure Test | 11/16/2015 | 11/16/2015 | 11/16/2015 | P | PASS |
Chad Schwendiman
|
|
|
Call Chuck ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss - 60lb gas pass, 20lb gas pass, 5lb flue pass
|
Rough-in | 11/4/2015 | 11/5/2015 | 11/5/2015 | A | FAIL |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss 1) gas test failed 2) flue test failed 3) remove concentric reducer from horizontal flue 4) missing supply in master (170cfm) 5) nail plate at dryer exhaust on 1st floor 6) need combustion air for the water heater from someplace other than the mechanically vented crawlspace.
|