Permit Information
Permit NumberMEC15-05876
StatusFinaled
Name PAIGE MECHANICAL GROUP INC
Site Address 2273 S VISTA AVE Unit: 100
Project Name 
Customer Number15.6198
ePlanReviewNo
Description
Alteration: Install:
Make Up Air
RTU
EF-2
Duct
Grille and Registers
Air Balance
Controls
Gas Piping
Condensate
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/18/20162/18/20162/18/2016PPASS
DetailsBen Livingston
Final2/17/20162/18/20162/18/2016AFAIL
DetailsBen Livingston
Phone #: ###-#### Inspection requested via web by Nicholas Paige- need air balance report for class 1 hood and makeup air
Rough-in2/15/20162/16/20162/16/2016APASS
DetailsChad Schwendiman
Grease Duct Final
Please call prior to arriving so we can meet you onsite.

thanks,
Phone #: ###-#### Inspection requested via web by Nicholas Paige
Rough-in2/11/20162/11/20162/11/2016PPASS
DetailsChad Schwendiman
grease duct inspection- Call john burks 1 hr prior to arriving so we can meet you onsite Phone #: ###-#### Inspection requested via web by Nicholas Paige - light test pass, okay to cover ceiling except for around the grease duct.
Rough-in2/10/20162/11/20162/11/2016AFAIL
DetailsChad Schwendiman
grease duct inspection Please call 1 hr proir to arriving so we can meet you onsite Phone #: ###-#### Inspection requested via web by Nicholas Paige - need to fix hole in grease duct and retest
Pressure Test1/20/20161/21/20161/21/2016PPASS
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Nicholas Paige - 60lb gas pass
Pressure Test1/20/20161/20/20161/20/2016PCANC
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Nicholas Paige - rescheduled for tomorrow afternoon
Rough-in1/20/20161/20/20161/20/2016PPART
DetailsChad Schwendiman
Partial Gas Rough in- Please call Jason with any questions Phone #: ###-#### Inspection requested via web by Nicholas Paige - okay to cover wall where hood goes
Conference1/14/20161/14/20161/14/2016PDONE
DetailsChad Schwendiman
fire damper and duct insulation Phone #: ###-#### Inspection requested via web by Nicholas Paige - Need to install fire dampers per the manufactures instructions
Rough-in1/6/20161/7/20161/7/2016APART
DetailsChad Schwendiman
Duct wrap Phone #: ###-#### Inspection requested via web by Nicholas Paige - okay to insulate the ductwork.