Final | 5/10/2016 | 5/10/2016 | 5/10/2016 | P | PASS |
Eric Strole
|
|
|
|
Final | 5/9/2016 | 5/10/2016 | 5/10/2016 | A | PART |
Eric Strole
|
|
|
Bj 5730755 Inspection requested via web by william kerwin-Need air balance reports.
|
Pressure Test | 1/20/2016 | 1/20/2016 | 1/20/2016 | P | PASS |
Eric Strole
|
|
|
20 lb gas test pass.
|
Rough-in | 1/20/2016 | 1/20/2016 | 1/20/2016 | P | PASS |
Eric Strole
|
|
|
|
Rough-in | 1/20/2016 | 1/20/2016 | 1/20/2016 | P | PASS |
Chad Schwendiman
|
|
|
Meet BJ and Eric at 1:00
|
Rough-in | 1/19/2016 | 1/20/2016 | 1/20/2016 | A | FAIL |
Eric Strole
|
|
|
Bj 5730755 Inspection requested via web by william kerwin-Rough-in needs to be per approved plans. Need approved plans on site.
|
Pressure Test | 1/19/2016 | 1/20/2016 | 1/20/2016 | A | CANC |
Eric Strole
|
|
|
Bj 5730755 Inspection requested via web by william kerwin
|
Pressure Test | 1/14/2016 | 1/14/2016 | 1/14/2016 | A | FAIL |
Eric Strole
|
|
|
Call monte to meet you there with ladders. 9724667. Or bj at 5730766. Please give 30 minutes notice. Thank You Inspection requested via web by william kerwin-Gas test fail.
|
Rough-in | 1/14/2016 | 1/14/2016 | 1/14/2016 | A | FAIL |
Eric Strole
|
|
|
Call monte to meet you there with ladders. 9724667. Or bj at 5730766. Please give 30 minutes notice. Thank You Inspection requested via web by william kerwin-Duct sizing is not per the approved plans.
|
Pressure Test | 12/29/2015 | 12/29/2015 | 12/29/2015 | P | CANC |
Eric Strole
|
|
|
Bj 5730755 Inspection requested via web by william kerwin
|
Rough-in | 12/29/2015 | 12/29/2015 | 12/29/2015 | P | FAIL |
Eric Strole
|
|
|
Bj 5730755 Inspection requested via web by william kerwin-No changes made. Need to protect condensate from freezing. Need to resummit manual-j or install per manual-j.
|
Pressure Test | 12/23/2015 | 12/23/2015 | 12/23/2015 | P | FAIL |
Chad Schwendiman
|
|
|
BJ ###-#### Inspection requested via web by william kerwin - No acces to furnaces or gauges in the attic
|
Rough-in | 12/23/2015 | 12/23/2015 | 12/23/2015 | P | FAIL |
Chad Schwendiman
|
|
|
BJ ###-#### Inspection requested via web by william kerwin - No access to city approved plans, No access to furnaces in attic, Need a 24" wide walk way from attic access to the service platform for furnace, need a 30"x30" service platform in front of the furnace in the attic, Need nail plates on dryer vents
|