Final | 8/11/2017 | 8/14/2017 | 8/14/2017 | A | PASS |
Brian Scoles
|
|
|
JOB IS READY FOR FINAL INSPECTION, DUCT BLAST AND BALANCE HAVE PASSED. VACANT HOME AND GARAGE CODE IS 4320. IF YOU ABSOLUTELY NEED SOMEONE TO MEET YOU ONSITE I GAVE YOU MY PHONE NUMBER AND GIVE ME 30 MINS HEADS UP AND I CAN MEET YOU ONSITE, MY NAME IS STEVE DALE - ###-#### Phone #: ###-#### Inspection requested via web by Rick Montgomery
|
Final | 7/31/2017 | 8/1/2017 | 8/1/2017 | P | FAIL |
Chad Schwendiman
|
|
|
Rick Montgomery and Carlos had a conversation a year ago when the original permit was pulled and it was decided that since this permit was pulled before the code changed of having to have the duct balance and blast before final inspection was not necessary for this permit since it was pulled before that code changed. Signed Manual J is onsite and we are ready for final mechanical inspection. VACANT HOME- GARAGE CODE- 4320. I have Owen our install managers number listed here if you need him to meet you there onsite or if you have any questions about the job. Phone #: ###-#### Inspection requested via web by Rick Montgomery - Permit was pulled after the requirment for ACCA reports, along with duct blasts, and air balances. Need to perform duct blast, and air balance prior to final inspection.
|
Mec-Aging Inspection | 7/19/2017 | 7/19/2017 | 7/19/2017 | | CANC |
Brian Scoles
|
|
|
no calls
|
Mec-Aging Inspection | 4/19/2017 | 4/19/2017 | 4/19/2017 | | PEND |
Brian Scoles
|
|
|
no calls
|
Mec-Aging Inspection | 1/18/2017 | 1/18/2017 | 1/18/2017 | | PEND |
Brian Scoles
|
|
|
talked with contractor- said job is on hold- they will check into this to see when final can be done and schedule if needed- WIP
|
Mec-Aging Inspection | 10/19/2016 | 10/19/2016 | 10/19/2016 | | CANC |
Brian Scoles
|
|
|
|
Rough-in | 5/23/2016 | 5/23/2016 | 5/23/2016 | P | PASS |
Chad Schwendiman
|
|
|
Rough In Inspection. Technician, Glen, will be on site. Please call him when you are on your way. ###-#### Phone #: ###-#### Inspection requested via web by Rick Montgomery - 20lb gas
|
Rough-in | 5/19/2016 | 5/20/2016 | 5/20/2016 | A | FAIL |
Chad Schwendiman
|
|
|
Re inspection. Approved Manual J is on site. Phone #: ###-#### Inspection requested via web by Rick Montgomery - 1) Need to use b-vent for furnace in uncoditioned space 2) Need 6" fresh air to return air plenum 3) Duct not sized per manual J 4) Need to seal joint on dryer duct 5) Need balance dampers on all supply runs
|
Rough-in | 5/18/2016 | 5/18/2016 | 5/18/2016 | P | FAIL |
Eric Strole
|
|
|
Inspection requested via web by Rick Montgomery-No approved manual-j on site. Reinspection fee issued.
|
Rough-in | 5/6/2016 | 5/9/2016 | 5/9/2016 | A | FAIL |
Chad Schwendiman
|
|
|
Need rough in Mechanical. Please call Glen ###-#### when in route and he will meet you there. Manual J is on site. Phone #: ###-#### Inspection requested via web by Rick Montgomery - Still need to submit a manual j for approval and have approved copy on site. still missing exhaust fans.
|
Rough-in | 3/28/2016 | 3/28/2016 | 3/28/2016 | P | FAIL |
Chad Schwendiman
|
|
|
Inspection requested via web by Rick Montgomery 1) need to submitt a manaul J and have it approved and a copy of the approved manual J onsite. 2) missing exhaust fans. 3) ducting not complete 4) need access to inspect furnace in the attic. 5) 20lb gas fail
|