Final | 6/20/2016 | 6/21/2016 | 6/21/2016 | A | PASS |
Chad Schwendiman
|
|
|
Jim Phone #: ###-####
|
Final | 6/10/2016 | 6/13/2016 | 6/13/2016 | A | FAIL |
Chad Schwendiman
|
|
|
Jim Phone #: ###-#### 1) Need economizer and power exhaust on roof top unit per approved plans 2) Need duct mounted smoke detector on return air duct per approved plans 3) Water heater flue needs to terminate 10' away or 3' above any fresh air opening into the building
|
Pressure Test | 6/1/2016 | 6/2/2016 | 6/2/2016 | A | PART |
Chad Schwendiman
|
|
|
Jim Phone #: ###-#### - 60lb gas pass from main to water heater, and from main to roof top
|
Rough-in | 5/9/2016 | 5/10/2016 | 5/10/2016 | A | PART |
Chad Schwendiman
|
|
|
Jim Phone #: ###-#### - duct work okay. okay to cover walls. Need to test gas piping at 60lbs on a 100lb gauge
|