Permit Information
Permit NumberMEC16-01980
StatusFinaled
Name ROYS PLUMBING
Site Address 1114 W FRONT ST Unit: 102
Project NameManfred's
Customer Number 
ePlanReviewNo
Description
HCAV new system-roof top unit
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/20/20166/21/20166/21/2016APASS
DetailsChad Schwendiman
Jim Phone #: ###-####
Final6/10/20166/13/20166/13/2016AFAIL
DetailsChad Schwendiman
Jim Phone #: ###-####
1) Need economizer and power exhaust on roof top unit per approved plans
2) Need duct mounted smoke detector on return air duct per approved plans
3) Water heater flue needs to terminate 10' away or 3' above any fresh air opening into the building
Pressure Test6/1/20166/2/20166/2/2016APART
DetailsChad Schwendiman
Jim Phone #: ###-#### - 60lb gas pass from main to water heater, and from main to roof top
Rough-in5/9/20165/10/20165/10/2016APART
DetailsChad Schwendiman
Jim Phone #: ###-#### - duct work okay. okay to cover walls. Need to test gas piping at 60lbs on a 100lb gauge