Permit Information
Permit NumberMEC16-02258
StatusFinaled
Name TVR INC
Site Address 800 W IDAHO ST Unit: 120
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Install owner provided Trane Equipment including controls (conduit and wire by others)
Install owner provided hood, exhaust fan and Mau for kitchen (ansul system and controls by others)
Provide and Install 1 each Cook Supply fa
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/24/20168/26/20168/26/2016APASS
DetailsChad Schwendiman
final - call tony Phone #: ###-#### Inspection requested via web by Brandon Sorensen
Final8/24/20168/24/20168/24/2016PPART
DetailsChad Schwendiman
as per Chad S. ok for temp C of O
Rough-in8/22/20168/23/20168/23/2016APASS
DetailsChad Schwendiman
first layer fire wrap - mid morning around 10am Phone #: ###-#### Inspection requested via web by Brandon Sorensen - 1st and 2nd layer fire wrap pass
Final8/19/20168/22/20168/22/2016PPART
DetailsChad Schwendiman
Final - call tony Phone #: ###-#### Inspection requested via web by Brandon Sorensen - temporary occupancy okay. Still need to complete fire wrap on grease duct on the roof
Rough-in8/18/20168/18/20168/18/2016PPASS
DetailsChad Schwendiman
Cover for kitchen Phone #: ###-#### Inspection requested via web by Brandon Sorensen - okay to cover grid ceiling
Rough-in8/15/20168/16/20168/16/2016APART
DetailsChad Schwendiman
2nd layer of fire wrap - late am Phone #: ###-#### Inspection requested via web by Brandon Sorensen -2nd layer pass above hood
Rough-in8/15/20168/15/20168/15/2016PFAIL
DetailsChad Schwendiman
2nd layer fire wrap Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Fire wrap needs to be banded per manufactures instructions
Rough-in8/15/20168/15/20168/15/2016PCANC
DetailsChad Schwendiman
2nd layer of fire wrap Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen Inspection cancelled from web by: Brandon Sorensen
Rough-in8/12/20168/12/20168/12/2016PPART
DetailsChad Schwendiman
first layer fire wrap - call tony Phone #: ###-#### Inspection requested via web by Brandon Sorensen - 1st layer fire wrap okay on top of hood
Rough-in8/11/20168/12/20168/12/2016APART
DetailsChad Schwendiman
Grease Duct Light Test - as per Bill - schedule inspection for early AM and tent ductwork with visqueen for light test - call Tony - on roof Phone #: ###-#### Inspection requested via web by Brandon Sorensen - grease duct light test pass for duct in alley and on roof to fan
Rough-in8/10/20168/11/20168/11/2016APART
DetailsChad Schwendiman
early morning light test for grease duct - call tony Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Grease duct light test pass for duct above the hood. not able to test duct outside of the building today
Rough-in8/4/20168/5/20168/5/2016APART
DetailsChad Schwendiman
ceiling cover in kitchen Phone #: ###-#### Inspection requested via web by Brandon Sorensen - okay to cover grid ceiling in the kitchen except for in front of the kitchen hood
Rough-in7/14/20167/15/20167/15/2016APART
DetailsChad Schwendiman
inspection of shaft ductwork Phone #: ###-#### Inspection requested via web by Brandon - okay to cover shafts in the 1st floor and 2nd floor
Conference7/12/20167/13/20167/13/2016ADONE
DetailsChad Schwendiman
conference for kitchen - clearance questions Phone #: ###-#### Inspection requested via web by Brandon Sorensen - meet and discussed the clearance to combustables required above the class 1 hood.
Rough-in7/6/20167/6/20167/6/2016PPASS
DetailsBen Livingston
First layer fire wrap inspection at our shop.2925 S Cole RD Boise ID Phone #: ###-#### Inspection requested via web by David Tully
Conference7/1/20167/5/20167/5/2016APASS
DetailsBen Livingston
Cover Inspection for chase and soffit duct. Phone #: ###-#### Inspection requested via web by David Tully- 2 chases, and soffit ok to cover
Conference6/21/20166/21/20166/21/2016PDONE
DetailsChad Schwendiman
Conference with Tony concerning Grease Duct at Eureka Phone #: ###-#### Inspection requested via web by Brandon Sorensen - met with Tony on site to discuse the routing of the grease duct. It currently is planned to pass through the exterior wall on the 2nd floor and duct up to the roof. They were asking if there was a issue with it passing through the exterior wall on the 1st floor instead and ducting up to the roof. I said I don't have a issue with it, but to check with achd since it is in a alley way.
Rough-in6/14/20166/15/20166/15/2016APART
DetailsChad Schwendiman
sealer inspection and conference for grease duct Phone #: ###-#### Inspection requested via web by Brandon Sorensen - duct seal pass