Final | 10/6/2016 | 10/7/2016 | 10/7/2016 | A | PASS |
Ben Livingston
|
|
|
Kolt Phone #: ###-####
|
Final | 10/5/2016 | 10/5/2016 | 10/5/2016 | P | FAIL |
Ben Livingston
|
|
|
Mark Phone #: ###-#### Armaflex needs uv protction, linestes need to be in a sleeve where they touch the ground, openings where they enter the building need to be sealed up, bvent needs 1" clearence to combustibles all vent piping needs to be fastened with 3 screws 2nd dairy condensate needs to be run
|
Rough-in | 6/15/2016 | 6/15/2016 | 6/15/2016 | P | PASS |
Ben Livingston
|
|
|
Please call for access - Mark Phone #: ###-#### x2 20lb gas rough in
|
Rough-in | 6/10/2016 | 6/10/2016 | 6/10/2016 | P | FAIL |
Ben Livingston
|
|
|
Mark Phone #: ###-####- all bed rooms need transfers,, both gs pressure gages under 20 lb
|
Rough-in | 5/26/2016 | 5/26/2016 | 5/26/2016 | P | FAIL |
Ben Livingston
|
|
|
would like call ahead; Marc Phone #: ###-####- you need accor report for these unites
|
Rough-in | 5/24/2016 | 5/25/2016 | 5/25/2016 | A | FAIL |
Ben Livingston
|
|
|
Mark Phone #: ###-####- couldnt get in, armaflex needs u v protection
|