Mechanical permit to change out the furnace and A/C in 3919 and 3921. ***5-26-16 customer added a gas line to the scope of work /CEV
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/6/201610/7/201610/7/2016APASS
DetailsBen Livingston
Kolt Phone #: ###-####
Final10/5/201610/5/201610/5/2016PFAIL
DetailsBen Livingston
Mark Phone #: ###-####
Armaflex needs uv protction, linestes need to be in a sleeve where they touch the ground, openings where they enter the building need to be sealed up,
bvent needs 1" clearence to combustibles
all vent piping needs to be fastened with 3 screws
2nd dairy condensate needs to be run
Rough-in6/15/20166/15/20166/15/2016PPASS
DetailsBen Livingston
Please call for access - Mark Phone #: ###-####
x2 20lb gas rough in
Rough-in6/10/20166/10/20166/10/2016PFAIL
DetailsBen Livingston
Mark Phone #: ###-####- all bed rooms need transfers,, both gs pressure gages under 20 lb
Rough-in5/26/20165/26/20165/26/2016PFAIL
DetailsBen Livingston
would like call ahead; Marc Phone #: ###-####- you need accor report for these unites
Rough-in5/24/20165/25/20165/25/2016AFAIL
DetailsBen Livingston
Mark Phone #: ###-####- couldnt get in, armaflex needs u v protection