Final | 8/2/2016 | 8/2/2016 | 8/2/2016 | P | PASS |
Brian Scoles
|
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen
|
Final | 8/1/2016 | 8/1/2016 | 8/1/2016 | P | PART |
Brian Scoles
|
|
|
Request inspection late in the day. Owner is trying to get occupancy today, tenant lease is expired at other location and needs to move in .Travis is onsite duct returns and corrected - inspection corrections. Phone #: ###-#### Inspection requested via web by David Tully - need to fix remaining corrections and temperary occupancy ok
|
Conference | 7/29/2016 | 7/29/2016 | 7/29/2016 | P | DONE |
Chad Schwendiman
|
|
|
Meet Brian to walk inspection with him.
|
Final | 7/29/2016 | 7/29/2016 | 7/29/2016 | P | FAIL |
Brian Scoles
|
|
|
rough / final Phone #: ###-#### Inspection requested via web by Brandon Sorensen -need b vent in conditioned space for furnace-need 1" clearance on b vent- condensate not completed in attic- filter on R/A side of furnace- need service platform in attic- water heater flue needs completed- need to remove tape from b vent seams- need 2nd condensate drains or wey switches on basement- need to remove all combustibles that dont meet 25/50 flame/smoke spread in R/A plenum
|
Rough-in | 7/29/2016 | 7/29/2016 | 7/29/2016 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen Inspection cancelled from web by: Brandon Sorensen
|