Conference | 10/20/2016 | 10/20/2016 | 10/20/2016 | A | DONE |
Brian Scoles
|
|
|
Meet on Job to go over kitchen equipment under class 1 hoods
|
Final | 10/19/2016 | 10/20/2016 | 10/20/2016 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige
|
Final | 10/13/2016 | 10/14/2016 | 10/14/2016 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige - Need air balance report for class 1 hoods, all equipment needs to be in place under the hoods to verify clearances, Exhuast and flues need to terminate 10' away or 3' above fresh air intakes
|
Rough-in | 10/3/2016 | 10/4/2016 | 10/4/2016 | A | PASS |
Chad Schwendiman
|
|
|
please call ernie with any questions Phone #: ###-#### Inspection requested via web by Nicholas Paige - okay to cover ceilings
|
Rough-in | 9/28/2016 | 9/29/2016 | 9/29/2016 | A | PART |
Chad Schwendiman
|
|
|
Fire Wrap Phone #: ###-#### Inspection requested via web by Nicholas Paige - 1st layer pass
|
Rough-in | 9/28/2016 | 9/28/2016 | 9/28/2016 | P | PASS |
Chad Schwendiman
|
|
|
grease duct Phone #: ###-#### Inspection requested via web by Nicholas Paige
|
Rough-in | 9/26/2016 | 9/28/2016 | 9/28/2016 | A | PART |
Chad Schwendiman
|
|
|
please give john a call a cover/Grease duct inspection Phone #: ###-#### Inspection requested via web by Nicholas Paige - light test okay. need to have 1/4" per foot slope on horizontal grease duct. need to reschedule to check slope once corrected
|