Final | 11/9/2016 | 11/10/2016 | 11/10/2016 | P | PASS |
Alan Hauser
|
|
|
|
Rough-in | 10/6/2016 | 10/7/2016 | 10/7/2016 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- correction need made on (4) register boots living room and dining room per manual J sizes- these 4 register are being resubmitted to city- according to contractor to the sizes installed- if air flow does not balance they will change to 10x6- all crawl duct is per manual j just boots are sized due to joyce spacing- check this on final
|
Rough-in | 10/5/2016 | 10/6/2016 | 10/6/2016 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- living room and dining room register boots are undersized for cfm- crawl needs to be complete with ducting- left correction notice on living room window
|
Pressure Test | 10/5/2016 | 10/6/2016 | 10/6/2016 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass
|