Final | 9/23/2016 | 9/26/2016 | 9/26/2016 | A | PASS |
Brian Scoles
|
|
|
This home is not Occupied. Please contact Richard the project manager before going to do inspection. The water heater will need to be inspected as per Bill. The lock code for home is 5150. Phone #: ###-#### Phone #: ###-#### Inspection requested via web by patrick graves
|
Final | 9/21/2016 | 9/23/2016 | 9/23/2016 | A | FAIL |
Brian Scoles
|
|
|
This home is not Occupied. Please contact Richard the project manager before going to do inspection. The water heater will need to be inspected as well per Bill. The lock code for home is 5150. Phone #: ###-#### Inspection requested via web by patrick graves- need 6 inch clearance to combustible single wall pipe- secondary drain ran to floor on coil- pan under water heater- pop off and drain from pan on water heater to garage floor
|
Final | 9/15/2016 | 9/15/2016 | 9/15/2016 | P | FAIL |
Ben Livingston
|
|
|
THE HOUSE IS VACANT. THE LOCK BOX IS 5150. PLEASE CALL RICHARD at ###-#### AN HOUR before going to do the Inspection Phone #: ###-#### Inspection requested via web by patrick graves water heater needs to be under a plumbing permit, water line has a kink in it b vent needs 1" clearance to combustables, single wall needs 6" clearance, wye needs to be replaced, need c.o alarms by bedrooms,
|