Final | 1/18/2018 | 1/19/2018 | 1/19/2018 | P | PASS |
Ben Livingston
|
|
|
Please call Aaron on your way up, I will be there to walk you through. Thanks! Phone #: ###-#### Inspection requested via web by john shay
|
Pressure Test | 11/15/2017 | 11/16/2017 | 11/16/2017 | P | PASS |
Ben Livingston
|
|
|
Please call Aaron with any questions. Thanks! Snow melt pressure test. Phone #: ###-#### Inspection requested via web by john shay 100lb hydronic test x2
|
Pressure Test | 10/30/2017 | 10/31/2017 | 10/31/2017 | A | PASS |
Ben Livingston
|
|
|
Please call Aaron with any questions. Thanks! Pressure test on snow melt. Phone #: ###-#### Inspection requested via web by john shay 1st 100lb test
|
Mec-Aging Inspection | 9/22/2017 | 9/22/2017 | 9/22/2017 | | PEND |
Bill VanDegrift
|
|
|
still working
|
Mec-Aging Inspection | 6/23/2017 | 6/23/2017 | 6/23/2017 | | CANC |
Ben Livingston
|
|
|
|
Conference | 3/24/2017 | 3/24/2017 | 3/24/2017 | P | PASS |
Ben Livingston
|
|
|
Bob Phone #: ###-#### okay to move hood back, per conversation
|
Rough-in | 10/16/2016 | 10/17/2016 | 10/17/2016 | P | PART |
Ben Livingston
|
|
|
Please call Aaron with any questions Phone #: ###-#### Inspection requested via web by john shay 60,20,lb gas 5lb flue x7 roughin only system in the crawl remains
|
Rough-in | 10/13/2016 | 10/14/2016 | 10/14/2016 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by john shay 5lb flue x7 ok, 20lb gas ok 60 lb gas needs to be per manufactures instruction fittingsn need to retest,
rough in nail plates on line sets and dryer vent
|