Conference | 12/20/2016 | 12/22/2016 | 12/22/2016 | A | DONE |
Chad Schwendiman
|
|
|
9:30 - Meeting w/Mark - ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg - Met Mark and he installed weather gasketing on the door
|
Final | 12/22/2016 | 12/22/2016 | 12/22/2016 | A | PASS |
Chad Schwendiman
|
|
|
9:30 - Meeting w/Mark - ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg
|
Conference | 12/7/2016 | 12/7/2016 | 12/9/2016 | P | PEND |
Bill VanDegrift
|
|
|
Our client is not willing to put any more money into this situation and has told our consultant that she doesn''t care if she doesn''t pass an inspection. We''d like a release waiver to have her sign that removes our responsibility in this situation. Thank you! Nicole ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg Talked to Jims, they are going to set up a time to meet on the project.
|
Final | 10/14/2016 | 10/18/2016 | 10/18/2016 | P | FAIL |
Chad Schwendiman
|
|
|
Please call Kyle @ ###-#### to make sure he''s ready for you. Thank you! Phone #: ###-#### Inspection requested via web by Rick Borg - Gas fired Furncaes are not allowed to be installed in a closet in a bedroom unless they are a direct vent appliance installed in accordance with the conditions of the listing, or the closet is used for no other purpose and is provided with a solid weather-stripped door equipped with a approved self closing device, and all combustion air is taken directly from the outdoors
|