Final | 11/3/2017 | 11/3/2017 | 11/3/2017 | A | PASS |
Brian Scoles
|
|
|
|
Mec-Aging Inspection | 10/31/2017 | 10/31/2017 | 10/31/2017 | | PART |
Brian Scoles
|
|
|
|
Mec-Aging Inspection | 8/1/2017 | 8/1/2017 | 8/1/2017 | | CANC |
Brian Scoles
|
|
|
|
Final | 4/28/2017 | 4/28/2017 | 4/28/2017 | P | PART |
Brian Scoles
|
|
|
Contact Antonio ###-#### Kevin will have TAB report and the building flush is starting today. Phone #: ###-#### Inspection requested via web by Dan Flaherty- 3 bvents for tube heaters exhaust side need clearance to combustibles at roof penetrations- talked with Antonio about this- temp occupancy ok
|
Rough-in | 4/25/2017 | 4/25/2017 | 4/26/2017 | P | PART |
Brian Scoles
|
|
|
Want to get a temporary occupancy. Contact Antonio 6023850 Phone #: ###-#### Inspection requested via web by Dan Flaherty- need precommissioning report and air balance report onsite for temp occupancy
|
Final | 4/18/2017 | 4/18/2017 | 4/18/2017 | P | CANC |
Chad Schwendiman
|
|
|
Antonio is the contact for final Phone #: ###-#### Inspection requested via web by Kim Adams
|
Rough-in | 3/30/2017 | 3/30/2017 | 3/30/2017 | P | PART |
Brian Scoles
|
|
|
Ceiling cover inspection. Contact Derek ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty- need to finish support and armor flex on linsets in various parts of building- register need covered for green building code- dryer exhauster needs support- ok for cover after these items have been addressed
|
Rough-in | 2/10/2017 | 2/10/2017 | 2/10/2017 | P | PART |
Brian Scoles
|
|
|
rough in Phone #: ###-#### Inspection requested via web by Crystal Grant- seal ok- ok to insulate
|
Rough-in | 1/26/2017 | 1/27/2017 | 1/27/2017 | P | PART |
Brian Scoles
|
|
|
Rough in inspection restrooms Phone #: ###-#### Inspection requested via web by Crystal Grant- 1st floor and 2nd floor restroom/shower seal ok- ok to insulate- ceiling was being rocked when i was their
|