Permit Information
Permit NumberMEC16-05130
StatusFinaled
Name ADVANCED HEATING & COOLING
Site Address 505 W BROAD STREET
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Supply and install all HVAC systems labor, materials, and equipment. HVAC equipment, accessories, and components. ERU MAU, heat pumps, fans, heaters, louvers, ductwork, registers, grills, dampers, drain pans, and condensing units.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/7/20183/7/20183/7/2018PPASS
DetailsChad Schwendiman
Final3/7/20183/7/20183/7/2018ACANC
DetailsChad Schwendiman
Final inspection for 710,610,510,410,310. Please contact Rob ###-#### with any questions or concerns Inspection requested via web by Heather Gransbery
Final3/6/20183/6/20183/6/2018PCANC
DetailsChad Schwendiman
Final inspection for 710,610,510,410,310. Please contact Rob ###-#### with any questions or concerns Inspection requested via web by Heather Gransbery
Final3/5/20183/5/20183/5/2018PFAIL
DetailsChad Schwendiman
Final inspection for 710,610,510,410,310. Please contact Rob ###-#### with any questions or concerns Phone #: ###-#### Inspection requested via web by Heather Gransbery - Anderson construction need to submit final LEED's commisioning report to boise city before we can final permit out.
Final3/2/20183/2/20183/2/2018PFAIL
DetailsChad Schwendiman
Final inspection for 710,610,510,410,310. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - air balancing not complete
Final3/1/20183/2/20183/2/2018AFAIL
DetailsChad Schwendiman
Final inspection for 710,610,510,410,310. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Jess Wigley - air balance needs to be completed.
Final2/28/20183/1/20183/1/2018ACANC
DetailsChad Schwendiman
Final inspection for 710,610,510,410,310. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Final2/9/20182/9/20182/9/2018PPART
DetailsChad Schwendiman
3rd, & 4th floors - Temporary occupancy okay for 3rd, and 4th floors
Final2/9/20182/12/20182/9/2018ACANC
DetailsChad Schwendiman
Request for 3rd floor final inspection Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Final2/8/20182/8/20182/8/2018APEND
DetailsChad Schwendiman
Final inspection rquest for 710,610 510,410,310. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - need a updated air balance report
Final2/2/20182/2/20182/2/2018PPART
DetailsChad Schwendiman
Request for final on Floors 5,6,7. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - temporary occupancy okay for 5th, 6th, and 7th floors.
Final1/25/20181/26/20181/26/2018AFAIL
DetailsChad Schwendiman
Request for Final/TCO FL 1, 2, 5, 6, 7. Please contact Rob with any questions or concerns ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need a copy of the air balance report for all area's being occupied. Need approved TCO plan from building official. Need to extend fresh air opening on roof.
Final1/16/20181/17/20181/17/2018APART
DetailsChad Schwendiman
request for final inspection on 3rd floor. No inspection on RM 310 and 312. Please contact Rob with any questions or concerns. ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 3rd floor units okay, unit 725 okay
Final1/15/20181/16/20181/16/2018ACANC
DetailsChad Schwendiman
Request for final inspection on 3rd floor. No inspection on RM 310 and 321. Please contact Rob with ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Final1/12/20181/12/20181/12/2018APART
DetailsChad Schwendiman
Request for final inspection on 4th floor. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Still need air balance report to final out units, 4th floor units okay, 5th floor trash room, and 532 okay. 634 okay, and 7th floor units okay
Final1/4/20181/5/20181/5/2018APEND
DetailsChad Schwendiman
Request for final inspection on 6th and 7th floors, except 610 and 710. Please contact Rob ###-#### with any questions or concerns.
Phone #: ###-#### Inspection requested via web by Heather Gransbery - Still need air balance reports to be able to final rooms out. 6th floor west side okay except for the corridoor. 5th floor west side okay except for 532 trash room and the corridoor
Rough-in11/21/201711/22/201711/22/2017APASS
DetailsChad Schwendiman
Request for inspection on trash room ceiling Floors 6-7. Please contact Rob, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 6th and 7th floor trash rooms okay to cover
Rough-in11/21/201711/21/201711/21/2017PPART
DetailsChad Schwendiman
Request for inspection on trash rooms Floors 3-7. Please contact Rob, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery Phone #: ###-#### Inspection requested via web by Heather Gransbery - Trash room ceilings okay to cover on 3rd, 4th, and 5th floors. 6th and 7th floors still need sheetrock removed to see duct
Rough-in11/20/201711/21/201711/21/2017AFAIL
DetailsChad Schwendiman
Request for inspection on trash rooms Floors 3-7. Please contact Rob, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - need to remove sheetrock to expose ductwork for inspection in trash rooms
Rough-in10/10/201710/11/201710/11/2017APASS
DetailsChad Schwendiman
Request for inspection 3rd floor R/I. Please contact Juan, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 3rd floor apartments okay
Rough-in10/4/201710/10/201710/10/2017APART
DetailsChad Schwendiman
Request for inspection 3rd floor. Please contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - units 323 - 328 okay
Rough-in9/25/20179/25/20179/25/2017APASS
DetailsChad Schwendiman
Request for inspection on 4th floor apts. Please contact Rob, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 4th floor apartments okay
Rough-in9/21/20179/21/20179/21/2017ACANC
DetailsChad Schwendiman
Rob - ###-####
Rough-in9/19/20179/19/20179/19/2017PPASS
DetailsChad Schwendiman
Request for R/I inspection 4th floor. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 4th floor unit 24 okay
Rough-in9/18/20179/18/20179/18/2017APASS
DetailsChad Schwendiman
Request for R/I inspection 4th and 5th floors. Please contact ROb, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 5th floor units 23, 24, 25, 26, 28, 29
Rough-in9/14/20179/14/20179/14/2017APASS
DetailsBen Livingston
Request for inspection r/I 5th floor. Please contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
527,532, 630,627 okay
Rough-in9/12/20179/13/20179/13/2017APART
DetailsBen Livingston
R/I inspection 6th floor. Contact Rob ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
rooms 530,531,631 okay
room 630 dryer vent has to many 90s
room 627 dryer vent has a dented pipe
Rough-in9/11/20179/12/20179/12/2017APASS
DetailsChad Schwendiman
Request for R/I inspection 6th Floor. Contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 6th floor units 23, 24, 28, 31, 32
Rough-in9/11/20179/11/20179/11/2017APASS
DetailsChad Schwendiman
Request for R/I inspection on 7th floor. Please contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Units 23, 24, 25, 26, 27, 28, 29, 30, 31, 32 okay to cover
Rough-in9/7/20179/7/20179/7/2017PPART
DetailsBen Livingston
Request for R/I above ceiling inspection 6th/7th. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
room 724 okay
Rough-in8/31/20179/1/20179/1/2017APASS
DetailsChad Schwendiman
r/I inspection request for 3-7th floor shafts. Please contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - subduct shaft 32 okay
Rough-in8/30/20178/31/20178/31/2017PPASS
DetailsChad Schwendiman
R/I inspection request for 3-th floor shafts. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 7th floor units 1, 2, 4, 5, 6, 7, 8 okay to cover
Rough-in8/4/20178/7/20178/7/2017PCANC
DetailsChad Schwendiman
request for shaft inspection 3rd through 7th floor. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Rough-in8/4/20178/7/20178/7/2017ACANC
DetailsChad Schwendiman
Request for shaft inspection 3rd through 7th floor. Please contact job lead, Rob, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Rough-in8/4/20178/4/20178/4/2017PPASS
DetailsChad Schwendiman
Request for inspection floors 3 through 7 shaft. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - sub duct shaft 27 complete
Rough-in8/3/20178/4/20178/4/2017APASS
DetailsChad Schwendiman
Inspection request for 3rd - 7th floor shafts. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - sub duct shaft 27 complete
Rough-in8/3/20178/3/20178/3/2017PCANC
DetailsChad Schwendiman
Inspection request for 3rd - 7th floor shafts. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in8/3/20178/3/20178/3/2017APASS
DetailsChad Schwendiman
Requesting AM inspection on Floors 3rd - 7th shaft inspection. Job lead contact is Rob Campbell ###-####. Phone #: ###-#### Inspection requested via web by Jess Wigley - sub duct shaft complete for units 29,30. ceilings okay to cover in units 625, 626
Rough-in8/1/20178/2/20178/3/2017PPASS
DetailsChad Schwendiman
Request for shaft inspection on floors 3-7th. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Sub duct shaft 30,31 complete, sub duct shaft 30,29 back partition okay, sub duct shaft 27 seal and caulk okay
Rough-in7/31/20178/1/20178/1/2017APASS
DetailsChad Schwendiman
Request for inspection on shafts 3-7th floor. Please contact job lead Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - back panel okay on sub duct shaft for 31, and 30 3rd floor to 7th. seal and caulk okay for sub duct shaft 30, and 29 3rd floor to 7th
Rough-in7/28/20177/31/20177/31/2017PCANC
DetailsChad Schwendiman
Request for shaft inspection 3rd through 7th floor. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Rough-in7/24/20177/24/20177/24/2017ACANC
DetailsChad Schwendiman
Request for inspection on 3rd through 7th floor shafts. Please contact job lead, Rob, with any questions or concerns. ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - This is the wrong permit number. I put notes in the right permit number.
Rough-in7/14/20177/14/20177/14/2017PPASS
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
subduct liner 11 complete 3rd to 7thfloor
**Inspection moved to MEC16-05454**
Rough-in7/13/20177/14/20177/14/2017APART
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather
Gransbery
subduct liner 8,10 complete
subduct 11 seal and caulk 3rd to 7th floor
**Inspection moved to MEC16-05454**
Rough-in7/12/20177/13/20177/13/2017APART
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns Phone #: ###-#### Inspection requested via web by Heather Gransbery
subduct liner 8,10 seal and caulk okay
subduct liner 12,14, 13,15 17 19 complete 3rd floor to 7th
**Inspection moved to MEC16-05454**
Rough-in7/11/20177/12/20177/12/2017APART
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns Phone #: ###-#### Inspection requested via web by Heather Gransbery
shaft liner 20,18,16 complete
shaft liner 12,14,19 seal and caulk
**Inspection moved to MEC16-05454**
Rough-in7/10/20177/11/20177/11/2017PNR
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
**Inspection moved to MEC16-05454**
Rough-in7/10/20177/10/20177/10/2017APART
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
subduct rooms 20,18,16,15 3rd floor to 7th seal and firecaulk inside okay
rooms 17,19 exhaust duct 3rd floor to 7th ok to start subduct **Inspection moved to MEC16-05454**
Mec-Aging Inspection6/21/20176/21/20176/21/2017 CANC
DetailsChad Schwendiman
wip