Final | 6/2/2017 | 6/5/2017 | 6/5/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino
|
Rough-in | 3/20/2017 | 3/21/2017 | 3/21/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
|
Rough-in | 3/16/2017 | 3/20/2017 | 3/20/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- supply register needs installed in bath #2 second level and flex needs hooked up- correction notice front window
|
Pressure Test | 3/16/2017 | 3/20/2017 | 3/20/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass- 5lb flue pass
|
Pressure Test | 3/16/2017 | 3/17/2017 | 3/16/2017 | P | CANC |
Eric Strole
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Rough-in | 3/16/2017 | 3/17/2017 | 3/16/2017 | P | CANC |
Eric Strole
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Pressure Test | 3/15/2017 | 3/16/2017 | 3/16/2017 | A | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- 20lb gas pass- 5lb flue test fail guage at zero
|
Rough-in | 3/15/2017 | 3/16/2017 | 3/16/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- flue guage at zero ps level 1 bath fan needs hooked up- bath #2 2nd level needs supply register installed and hooked up- b vent needs 1" clearance to combustiles water heater location at sheetrock ceiling- left correction notice front window
|