Permit NumberMEC17-00968
StatusFinaled
Name PERFORMANCE MECHANICAL INC
Site Address 2964 E PARKCENTER BLVD
Project Name 
Customer NumberPERF-BARB
ePlanReviewNo
Description
New: HVAC-multi family units only see MEC17-01004 is for the club house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/20/20177/21/20177/21/2017APASS
DetailsEric Strole
Reinspect Phone #: ###-#### Inspection requested via web by Aaron Allred
Final7/6/20177/6/20177/6/2017PFAIL
DetailsBen Livingston
For temp only - Anthony Phone #: ###-####
dryer vent lengths need to be posted in dryer boxs, need to verify 2nd condensate in houseing units, diffusers need to be fastened to grid
Rough-in6/22/20176/22/20176/22/2017APASS
DetailsEric Strole
3 fire/smoke dampers okay in storage room. This inspection was done on 6-12-17 by Chad Schwendiman under the wrong permit. (RW)
Rough-in6/12/20176/12/20176/12/2017PPART
DetailsChad Schwendiman
Inspect 3 fire dampers. Phone #: ###-#### Inspection requested via web by Aaron Allred - 3 fire/smoke dampers okay in storage room
Rough-in6/2/20176/2/20176/2/2017PPART
DetailsBen Livingston
System 4 Phone #: ###-#### Inspection requested via web by Aaron Allred
high lobby duct okay
Rough-in5/18/20175/18/20175/18/2017PPASS
DetailsBen Livingston
Phone #: ###-#### Inspection requested via web by Aaron Allred
hallway fire smoke clearence and angle insp. okay, angle insp. restroom and closet fire smokes okay,
Rough-in5/16/20175/16/20175/16/2017PCANC
DetailsEric Strole
8 units on 5th floor Phone #: ###-#### Inspection requested via web by Aaron Allred
Rough-in5/15/20175/15/20175/15/2017PFAIL
DetailsEric Strole
Aaron Phone #: ###-####-Changes not complete from correction notice.
Rough-in5/12/20175/12/20175/12/2017PFAIL
DetailsEric Strole
Commercial fire damper. Phone #: ###-#### Inspection requested via web by Aaron Allred-Finish angle on fire/smoke damper in corridor. Uncover fire/smoke damper in shaft for inspection. REINSPECTION FEE ISSUED. NEED TO PAY FEE BEFORE NEXT INSPECTION.
Rough-in5/4/20175/5/20175/5/2017AFAIL
DetailsBen Livingston
Fire Damper Phone #: ###-#### Inspection requested via web by Aaron Allred
seal up screw holes in fire dampers, need to finish angles in hallway
Rough-in5/2/20175/3/20175/3/2017AFAIL
DetailsBen Livingston
6 Units Fire Damper Phone #: 435­691­1614 Inspection requested via

web by Aaron Allred Phone #: 435
angle needs to be tight in corners, no gaps
Rough-in5/2/20175/2/20175/2/2017PPART
DetailsEric Strole
6 Units Fire Damper Phone #: 435­691­1614 Inspection requested via

web by Aaron Allred Phone #: 435-Corrections complete, need to install rest of angle on fire/smoke dampers.
Rough-in5/2/20175/2/20175/2/2017PCANC
DetailsBen Livingston
6 Units Fire Damper Phone #: 435­691­1614 Inspection requested via

web by Aaron Allred Phone #: 435
Rough-in5/1/20175/1/20175/1/2017PFAIL
DetailsEric Strole
6 Units
Fire Damper Phone #: ###-#### Inspection requested via web by Aaron Allred-Need to use a minimum of 16 gauge angle on fire dampers. Need to use approved straping on metal ducting and dryer venting. Need to support dryer venting every 4' and metal ducting every 10'.
Rough-in5/1/20175/1/20175/1/2017PFAIL
DetailsBen Livingston
fire/smoke damper angle wrong gauge, dryer vents need support every 4ft, use approved duct hangers
Rough-in3/21/20173/22/20173/22/2017APASS
DetailsBen Livingston
Dryer vents and line-sets Phone #: ###-#### Inspection requested via web by Aaron Allred
bld 3 201-206 dryer vent and lineset prerock rough-in okay