Final | 7/20/2017 | 7/21/2017 | 7/21/2017 | A | PASS |
Eric Strole
|
|
|
Reinspect Phone #: ###-#### Inspection requested via web by Aaron Allred
|
Final | 7/6/2017 | 7/6/2017 | 7/6/2017 | P | FAIL |
Ben Livingston
|
|
|
For temp only - Anthony Phone #: ###-#### dryer vent lengths need to be posted in dryer boxs, need to verify 2nd condensate in houseing units, diffusers need to be fastened to grid
|
Rough-in | 6/22/2017 | 6/22/2017 | 6/22/2017 | A | PASS |
Eric Strole
|
|
|
3 fire/smoke dampers okay in storage room. This inspection was done on 6-12-17 by Chad Schwendiman under the wrong permit. (RW)
|
Rough-in | 6/12/2017 | 6/12/2017 | 6/12/2017 | P | PART |
Chad Schwendiman
|
|
|
Inspect 3 fire dampers. Phone #: ###-#### Inspection requested via web by Aaron Allred - 3 fire/smoke dampers okay in storage room
|
Rough-in | 6/2/2017 | 6/2/2017 | 6/2/2017 | P | PART |
Ben Livingston
|
|
|
System 4 Phone #: ###-#### Inspection requested via web by Aaron Allred high lobby duct okay
|
Rough-in | 5/18/2017 | 5/18/2017 | 5/18/2017 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Allred hallway fire smoke clearence and angle insp. okay, angle insp. restroom and closet fire smokes okay,
|
Rough-in | 5/16/2017 | 5/16/2017 | 5/16/2017 | P | CANC |
Eric Strole
|
|
|
8 units on 5th floor Phone #: ###-#### Inspection requested via web by Aaron Allred
|
Rough-in | 5/15/2017 | 5/15/2017 | 5/15/2017 | P | FAIL |
Eric Strole
|
|
|
Aaron Phone #: ###-####-Changes not complete from correction notice.
|
Rough-in | 5/12/2017 | 5/12/2017 | 5/12/2017 | P | FAIL |
Eric Strole
|
|
|
Commercial fire damper. Phone #: ###-#### Inspection requested via web by Aaron Allred-Finish angle on fire/smoke damper in corridor. Uncover fire/smoke damper in shaft for inspection. REINSPECTION FEE ISSUED. NEED TO PAY FEE BEFORE NEXT INSPECTION.
|
Rough-in | 5/4/2017 | 5/5/2017 | 5/5/2017 | A | FAIL |
Ben Livingston
|
|
|
Fire Damper Phone #: ###-#### Inspection requested via web by Aaron Allred seal up screw holes in fire dampers, need to finish angles in hallway
|
Rough-in | 5/2/2017 | 5/3/2017 | 5/3/2017 | A | FAIL |
Ben Livingston
|
|
|
6 Units Fire Damper Phone #: 4356911614 Inspection requested via
web by Aaron Allred Phone #: 435 angle needs to be tight in corners, no gaps
|
Rough-in | 5/2/2017 | 5/2/2017 | 5/2/2017 | P | PART |
Eric Strole
|
|
|
6 Units Fire Damper Phone #: 4356911614 Inspection requested via
web by Aaron Allred Phone #: 435-Corrections complete, need to install rest of angle on fire/smoke dampers.
|
Rough-in | 5/2/2017 | 5/2/2017 | 5/2/2017 | P | CANC |
Ben Livingston
|
|
|
6 Units Fire Damper Phone #: 4356911614 Inspection requested via
web by Aaron Allred Phone #: 435
|
Rough-in | 5/1/2017 | 5/1/2017 | 5/1/2017 | P | FAIL |
Eric Strole
|
|
|
6 Units Fire Damper Phone #: ###-#### Inspection requested via web by Aaron Allred-Need to use a minimum of 16 gauge angle on fire dampers. Need to use approved straping on metal ducting and dryer venting. Need to support dryer venting every 4' and metal ducting every 10'.
|
Rough-in | 5/1/2017 | 5/1/2017 | 5/1/2017 | P | FAIL |
Ben Livingston
|
|
|
fire/smoke damper angle wrong gauge, dryer vents need support every 4ft, use approved duct hangers
|
Rough-in | 3/21/2017 | 3/22/2017 | 3/22/2017 | A | PASS |
Ben Livingston
|
|
|
Dryer vents and line-sets Phone #: ###-#### Inspection requested via web by Aaron Allred bld 3 201-206 dryer vent and lineset prerock rough-in okay
|