Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberMEC17-00970
StatusFinaled
Name PERFORMANCE MECHANICAL INC
Site Address 2950 E PARKCENTER BLVD
Project NameArboretum at Barber Station #1
Customer Number 
ePlanReviewNo
Description
HVAC for for multi family units
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/1/20185/2/20185/2/2018APASS
DetailsEric Strole
Re-inspect plumbing drains on mini splits for C of O Phone #: ###-#### Inspection requested via web by Aaron Allred
Final5/1/20185/1/20185/1/2018PFAIL
DetailsBen Livingston
Re-inspect plumbing drains on mini splits for C of O Phone #: ###-#### Inspection requested via web by Aaron Allred
corrections not made
Final4/30/20184/30/20184/30/2018PFAIL
DetailsChad Schwendiman
Lyman ###-#### - Need to complete condensate on ductless units
Final4/27/20184/30/20184/30/2018APART
DetailsEric Strole
Units 309-319 and units 209-219 Phone #: ###-#### Inspection requested via web by Aaron Allred-Rooms 209 thru 219 & 309 thru 319 pass.
Final4/24/20184/25/20184/25/2018APART
DetailsBen Livingston
Units 409-419 and Units 509-519 Phone #: ###-#### Inspection requested via web by Aaron Allred
Rough-in4/19/20184/20/20184/20/2018APASS
DetailsBen Livingston
Above grid 2nd and 3rd floor corridors. Phone #: ###-#### Inspection requested via web by Aaron Allred
Rough-in4/16/20184/16/20184/16/2018PPASS
DetailsEric Strole
Above grid fourth floor corridor. Phone #: ###-#### Inspection requested via web by Aaron Allred
Rough-in4/12/20184/13/20184/13/2018APASS
DetailsBen Livingston
Above grid 5th floor corridor. Phone #: ###-#### Inspection requested via web by Aaron Allred
Final4/11/20184/12/20184/12/2018APART
DetailsEric Strole
Unit 201 through 208 Phone #: ###-#### Inspection requested via web by Aaron Allred-Rooms 201 thru 208 pass.
Final4/10/20184/11/20184/11/2018PPART
DetailsEric Strole
Unites 301-308 Phone #: ###-#### Inspection requested via web by Aaron Allred-Rooms 301 thru 308 pass.
Final4/10/20184/11/20184/11/2018APART
DetailsEric Strole
Unites 401-408 Phone #: ###-#### Inspection requested via web by Aaron Allred-Rooms 401 thru 408 pass.
Final4/10/20184/10/20184/10/2018PPART
DetailsEric Strole
Units 501-508 Phone #: ###-#### Inspection requested via web by Aaron Allred-Rooms 501 thru 508 pass.
Rough-in3/26/20183/27/20183/27/2018APART
DetailsEric Strole
Damper Angles Phone #: ###-#### Inspection requested via web by Aaron Allred-Angle inspection for fire/smoke dampers in shaft 2nd thru 5th pass.
Rough-in3/26/20183/26/20183/26/2018PFAIL
DetailsEric Strole
Damper Angles Phone #: ###-#### Inspection requested via web by Aaron Allred-Need to secure 1 sided angle installation on fire/smoke dampers 2nd thru 5th flr per manufacture installation instructions.
Rough-in3/23/20183/26/20183/26/2018APART
DetailsEric Strole
Four Floors
Phone #: ###-#### Inspection requested via web by Aaron Allred-Clearance on fire/smoke dampers in shaft 2nd thru 5th pass.
Rough-in3/8/20183/8/20183/8/2018PPART
DetailsEric Strole
5th 3rd fourth and 2nd tower one above grid corridors. Phone #: ###-#### Inspection requested via web by Aaron Allred-Above grid tower one 2nd thru 5th pass.
Rough-in3/6/20183/6/20183/6/2018PPART
DetailsBen Livingston
First Floor Lobby inspection. Phone #: ###-#### Inspection requested via web by Aaron Allred
lobby okay, 4th and 5th floor fire smoke dampers back side clearance ok, need fire caulk on pool heater fire stops, fasten out side fire stops and seal
Conference2/28/20182/28/20182/28/2018PPART
DetailsEric Strole
Conferance on fire/smoke damper in shaft.-Conferance and angle on fire/smoke dampers in shaft floor only 2nd thru 5th pass
Conference2/28/20182/28/20182/28/2018PPASS
DetailsBen Livingston
Conferance on fire/smoke damper in shaft.
Rough-in2/27/20182/28/20182/28/2018APART
DetailsEric Strole
3rd-floor lobby and 2nd-floor dampers Phone #: ###-#### Inspection requested via web by Aaron Allred-Angle inspection on fire/smoke dampers in lobby on 2nd flr and duct seal 2nd & 3rd flr lobby area pass.
Rough-in2/27/20182/27/20182/27/2018PPART
DetailsEric Strole
Fourth Floor Lobby Fire/Smoke Damper Angle Inspection. Phone #: ###-#### Inspection requested via web by Aaron Allred-Angles for 4th flr lobby fire/smoke dampers pass.
Rough-in2/26/20182/27/20182/27/2018APART
DetailsEric Strole
Fourth Floor Lobby Phone #: ###-#### Inspection requested via web by Aaron Allred-3rd, 4th, 5th flr duct seal in shaft & 4th flr lobby duct seal pass.
Rough-in2/23/20182/26/20182/26/2018APART
DetailsEric Strole
units 209 through 219 Phone #: ###-#### Inspection requested via web by Aaron Allred-units 209 thru 219 pass.
Rough-in2/20/20182/21/20182/21/2018APART
DetailsEric Strole
Building 1 Rough-in. Inspection requested for 2nd floor damper spacing. Phone #: ###-#### Inspection requested via web by Aaron Allred-Clearance on 3 fire/smoke dampers 2nd flr corridor pass.
Rough-in2/19/20182/20/20182/20/2018ANR
DetailsEric Strole
2nd floor damper spacing Phone #: ###-#### Inspection requested via web by Aaron Allred-Not ready
Rough-in2/7/20182/8/20182/8/2018APART
DetailsEric Strole
Units 309-319 Phone #: ###-#### Inspection requested via web by Aaron Allred-Units 309 thru 319 r/i pass.
Conference2/6/20182/6/20182/6/2018PPASS
DetailsBen Livingston
Rough-in2/5/20182/6/20182/6/2018APART
DetailsEric Strole
5th Floor Corridor Phone #: ###-#### Inspection requested via web by Aaron Allred-Angle inspection on 3 fire/smoke dampers 5th flr corridor pass & lobby duct seal pass.
Rough-in2/5/20182/5/20182/5/2018PPART
DetailsEric Strole
Dampening Phone #: ###-#### Inspection requested via web by Aaron Allred-clearances for 3 fire/smoke dampers in corridors on 3rd & 4th flr pass.
Rough-in1/16/20181/17/20181/17/2018APART
DetailsEric Strole
Lyman Phone #: ###-####-Clearance inspection on 3 fire/smoke dampers in corridor on 5th flr pass.
Rough-in1/11/20181/11/20181/11/2018PPART
DetailsEric Strole
Carson Phone #: ###-####-Ducting in units 409 thru 419 pass.
Rough-in1/2/20181/3/20181/3/2018APASS
DetailsBen Livingston
Ducting for units 509 - 519 - Lyman Phone #: ###-####
Rough-in1/2/20181/2/20181/2/2018PFAIL
DetailsEric Strole
Ducting for units 509 - 519 - Lyman Phone #: ###-####Need to support ducts every 8'.
Rough-in12/5/201712/5/201712/5/2017PPART
DetailsEric Strole
Unit 201-208 // Lyman Phone #: ###-####-Units 201 thru 208 pass.
Rough-in11/6/201711/7/201711/7/2017APASS
DetailsBen Livingston
Lyman Phone #: ###-####
301-308 okay
Rough-in11/1/201711/2/201711/2/2017APART
DetailsEric Strole
3rd and 4th corr. // Lymon Phone #: ###-####-4th flr corridor and west end of 3rd flr corridor pass.
Rough-in11/1/201711/1/201711/1/2017PPART
DetailsEric Strole
Building 2, floors 3,4,5- grid- Lyman Phone #: ###-####-5th flr grid & west side 4th flr grid pass.
Rough-in10/26/201710/27/201710/27/2017APASS
DetailsBen Livingston
Lyman Phone #: ###-####
401-408 okay
Rough-in10/18/201710/19/201710/19/2017APASS
DetailsBen Livingston
Fifth Floor 501-508 rooms. Phone #: ###-#### Inspection requested via web by Aaron Allred
501-508 duct soffits ok
Rough-in10/11/201710/12/201710/12/2017APART
DetailsBen Livingston
Dryer vent Phone #: ###-#### Inspection requested via web by Aaron Allred
dryer vents and linesets okay 4th and 5th floor north side of building and 209,309,409,508 except 518 dryer vent needs wall furred out
Rough-in9/6/20179/6/20179/6/2017PPART
DetailsEric Strole
unit 508 dryer vent // Aaron Phone #: ###-####-Inwall dryer exhaust and line-set pass 5th flr.
Rough-in9/5/20179/6/20179/6/2017AFAIL
DetailsEric Strole
Anthony Phone #: ###-####-Sheetrock has not been removed.
Rough-in8/31/20178/31/20178/31/2017APART
DetailsEric Strole
Dryer exhausts and line-sets 2nd & 3rd flr inwall pass except units 209,309,409 & 509 pass. Those other 4 units need the wall furred out for the dryer exhausts.
Rough-in8/30/20178/30/20178/30/2017PPART
DetailsEric Strole
Anthony Phone #: ###-####-dryer vents and line-sets in units 510 thru 516 & 519 & 520 and 4th flr ok to cover walls.