Final | 8/11/2017 | 8/14/2017 | 8/14/2017 | A | PASS |
Brian Scoles
|
|
|
garage code #0524 Phone #: ###-#### Inspection requested via web by Debbie Marino
|
Final | 8/10/2017 | 8/11/2017 | 8/11/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need to insulate 6" round duct for humidifier and support it in garage at furnace
|
Final | 8/9/2017 | 8/10/2017 | 8/9/2017 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Final | 8/2/2017 | 8/2/2017 | 8/2/2017 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Rough-in | 5/22/2017 | 5/23/2017 | 5/23/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
|
Conference | 5/22/2017 | 5/22/2017 | 5/22/2017 | P | DONE |
Chad Schwendiman
|
|
|
|
Rough-in | 5/22/2017 | 5/22/2017 | 5/22/2017 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need make up air for range hood- need transfer grill in laundry room for whole house ventilation- fresh air can not come from roof- need to draw exhaust air fir HRV from living space per manufactures installation diagram- left correction notice on front window- gave builder ok to spray foam exterior walls only
|
Pressure Test | 5/22/2017 | 5/22/2017 | 5/22/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass
|