Final | 9/5/2017 | 9/6/2017 | 9/6/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
|
Final | 9/1/2017 | 9/5/2017 | 9/5/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need duct blast test completed
|
Rough-in | 6/12/2017 | 6/13/2017 | 6/13/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino
|
Rough-in | 6/8/2017 | 6/9/2017 | 6/9/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- supply plenum in crawl needs insulated- bath fan in master bath needs hooked up- dryer vent 2nd floor needs support in wall or every 4 feet- R/A wye branch 2nd floor attic needs sealed- left correction notice front window
|
Pressure Test | 6/8/2017 | 6/9/2017 | 6/9/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass- 5 lb flue pass
|