Final | 12/5/2017 | 12/5/2017 | 12/5/2017 | P | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer
|
Final | 12/4/2017 | 12/5/2017 | 12/5/2017 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer - Need to pay reinspection fee prior to inspection
|
Final | 12/1/2017 | 12/4/2017 | 12/4/2017 | P | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer-Still no air balance report on site. Reinspection fee issued.
|
Final | 12/1/2017 | 12/1/2017 | 12/1/2017 | P | FAIL |
Eric Strole
|
|
|
Code - 2010 Call Mike - ###-#### 1/2 hr. before arrival. Phone #: ###-#### Inspection requested via web by Bryan Palmer-No air balance report on site
|
Final | 11/29/2017 | 11/29/2017 | 11/29/2017 | P | NH |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer no access
|
Final | 11/28/2017 | 11/29/2017 | 11/29/2017 | A | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer-No air balance report on site & need kitchen hood exhaust installed.
|
Rough-in | 8/28/2017 | 8/28/2017 | 8/28/2017 | P | PASS |
Ben Livingston
|
|
|
Call Mike Holmes if any questions. Phone #: ###-#### Inspection requested via web by Bryan Palmer
|
Rough-in | 8/18/2017 | 8/18/2017 | 8/18/2017 | P | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer-Suppy's and return's are not per the approved manual-j. Fresh air can not come off return can. Need to rough-in per the approved manual-j or re submit manual-j.
|
Rough-in | 8/17/2017 | 8/18/2017 | 8/18/2017 | A | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer-No approved manual-j on site.
|
Pressure Test | 8/17/2017 | 8/18/2017 | 8/18/2017 | A | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer-20 lb gas test pass.
|