Final | 1/4/2018 | 1/5/2018 | 1/5/2018 | A | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
|
Rough-in | 10/6/2017 | 10/6/2017 | 10/6/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- corrections made
|
Pressure Test | 10/6/2017 | 10/6/2017 | 10/6/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- 20lb gas pass- 5lb flue pass
|
Pressure Test | 10/5/2017 | 10/5/2017 | 10/5/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- gas test fail gauge below 20psi and gauge wont zero out- flue pressure gauge needs to be 15lb not 30lb gauge- need to retest both when complete
|
Rough-in | 10/5/2017 | 10/5/2017 | 10/5/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need insulation shield on b vent with 1" clearance and sheetrock needs 1" clearance to b vent or water heater- bath fan 2nd floor needs hooked up, fan missing- supply register needs sealed to floor entry from garage- master bath supply register needs sealed to floor- left correction notice front entry window
|