Permit Information
Permit NumberMEC17-04433
StatusFinaled
Name JM MECHANICAL
Site Address 348 S 13TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install Furnaces, Coils, Condensers, PTACs, RTUs, MAU''s, exhaust fans and ductwork.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/21/20189/24/20189/24/2018APASS
DetailsChad Schwendiman
John Phone #: ###-####
Final7/16/20187/16/20187/16/2018PPART
DetailsChad Schwendiman
John Phone #: ###-#### - Phase 2 temporary occupancy okay. Need final air balance report still
Rough-in7/12/20187/13/20187/13/2018PFAIL
DetailsChad Schwendiman
2nd layer fire wrap - John Phone #: ###-#### - Need to complete banding on 2nd layer, Need to complete furnace flue in kitchen, Need to address low air flows on balance report.
Rough-in7/12/20187/13/20187/13/2018APASS
DetailsChad Schwendiman
1st layer fire wrap - John Phone #: ###-#### - 1st layer fire wrap on the discharge side of the fans okay
Final7/11/20187/12/20187/12/2018AFAIL
DetailsChad Schwendiman
John Phone #: ###-####
1) Need to seal return duct in kitchen
2) Need to complete fire wrap on grease duct ( needs to be done by a certified individual).
3) Grease drain needs to be ran in Black iron, stainless steel, or copper.
4) Need to complete vent terminations on outside of building
5) Pool heater vents need to be installed per manufactures instructions.
6) Need to support duct at canvas connector on dehumidification unit.
7) Need final air balance report
8) Need to install intake hood on MAU for 1st floor
9) Need to protect insulation on outside duct for MAU 1st floor
Conference7/2/20187/2/20187/2/2018ADONE
DetailsChad Schwendiman
Phone # ###-####
Rough-in6/27/20186/28/20186/28/2018ACANC
DetailsChad Schwendiman
Travis--as early as possible Phone #: ###-####
Final6/28/20186/28/20186/28/2018PPART
DetailsChad Schwendiman
Travis--as early as possible Phone #: ###-#### - Phase 1 TCO okay. There are Deficiencies in the air balance report that need to be corrected proir to signing off on CO
Rough-in6/25/20186/26/20186/26/2018PPART
DetailsChad Schwendiman
Travis Phone #: ###-#### - Duct insulation okay on exterior ductwork
Conference6/19/20186/20/20186/20/2018ADONE
DetailsChad Schwendiman
Travis Phone #: ###-#### - Met to discuss clearance to combustables to grease fans
Rough-in6/13/20186/14/20186/14/2018APART
DetailsChad Schwendiman
2-5 floors- Travis Phone #: ###-#### - Guest rooms okay. missing panduits on flexs in corridoor, need to complete condensate and gas piping on furnaces in corridoors.
Rough-in6/1/20186/4/20186/4/2018APASS
DetailsChad Schwendiman
for grease duct insp // Travis Phone #: ###-#### - light test pass
Rough-in5/22/20185/23/20185/23/2018AFAIL
DetailsChad Schwendiman
early am- Travis Phone #: ###-#### - Grease duct light test fail. Need to weld up holes in grease duct, need 3" cleear space around grease duct for fire wrap, need 18" clearance to combustables above hood
Rough-in5/15/20185/16/20185/16/2018PPART
DetailsChad Schwendiman
1st floor R/I - Travis Phone #: ###-#### - Okay to cover lobby hard lids, pool room hard lid, and conference room hard lids
Rough-in5/9/20185/10/20185/10/2018APART
DetailsChad Schwendiman
Travis Phone #: ###-#### - Okay to cover lobby ceiling except for around missing return cans
Rough-in5/7/20185/8/20185/8/2018PFAIL
DetailsChad Schwendiman
Travis Phone #: ###-#### - need to complete rough in above lobby ceiling
Rough-in4/24/20184/25/20184/25/2018PPASS
DetailsChad Schwendiman
Travis Phone #: ###-#### - Okay to insulate duct on first floor splits, okay to cover ceilings in 1st floor guest rooms, east and west mechanical shafts okay, okay to cover ice machine ceilings on 2nd 3rd and 4th floors
Rough-in4/10/20184/11/20184/11/2018PPART
DetailsChad Schwendiman
Travis Phone #: ###-#### - Okay to cover ceiling in rooms 228, 328
Rough-in3/27/20183/27/20183/27/2018PPASS
DetailsChad Schwendiman
Travis Phone #: ###-#### - Okay to cover hard lids in corridoors 2-5th floors
Rough-in2/6/20182/7/20182/7/2018PPASS
DetailsChad Schwendiman
Travis Phone #: ###-#### - Okay to cover hard lids in the rooms on 2nd and 3rd floors
Rough-in2/1/20182/2/20182/2/2018PPASS
DetailsChad Schwendiman
Travis Phone #: ###-#### - okay to cover 5th floor hard lids
Rough-in1/19/20181/22/20181/22/2018APASS
DetailsBen Livingston
Travis Phone #: ###-####-9167
5lb flue x2, 5th floor ehaust drops in bathrooms,
corridor duct seal okay, 4th floor bathroom aboce cieling okay
Rough-in1/8/20181/8/20181/8/2018PPASS
DetailsChad Schwendiman
2nd fl above ceiling - Travis Phone #: ###-#### - Okay to cover hard lids in rooms 201-218
Rough-in12/19/201712/20/201712/20/2017APASS
DetailsChad Schwendiman
Travis Phone #: ###-#### - Okay to cover hard lids in rooms 301-310, okay to cover walls and tgi's on 2nd, 3rd and 4th, and 5th floors west end
Rough-in12/15/201712/15/201712/15/2017PPASS
DetailsChad Schwendiman
Travis Phone #: ###-#### - Okay to cover hard lids in rooms 401-410
Rough-in12/12/201712/13/201712/13/2017APASS
DetailsChad Schwendiman
Travis Phone #: ###-#### - Okay to cover hard lids in rooms 501-510
Rough-in12/7/201712/7/201712/7/2017PCANC
DetailsChad Schwendiman
Brian Phone #: ###-####
Rough-in12/6/201712/7/201712/7/2017APASS
DetailsChad Schwendiman
Travis ###-#### - Okay to cover TGI's in the 3rd floor corridoor
Rough-in12/6/201712/6/201712/6/2017PPASS
DetailsChad Schwendiman
Travis Phone #: ###-#### - Okay to cover bottom of tgi's in the corridoor on 2nd, 4th, and 5th floors
Conference11/30/201712/1/201712/1/2017APASS
DetailsBen Livingston
Travis Phone #: ###-####
when duct can be lowered to inspect the top for sealer okay, if not need to cut a hole to inspect from inside
Rough-in11/9/201711/9/201711/9/2017PPASS
DetailsChad Schwendiman
Late afternoon if possible // Travis Phone #: ###-#### Okay to cover walls and bottom of tgi's on 2nd and 3rd floors grid lines 1-12. 5th floor okay to cover exhaust plenums grid lines 1-12. Need to get approved plans on site prior to next inspection
Rough-in10/31/201710/31/201710/31/2017PPART
DetailsChad Schwendiman
Travis Phone #: ###-#### - Okay to cover walls in the east side of the 4th floor
Rough-in10/16/201710/16/201710/16/2017PPASS
DetailsBen Livingston
5th floor prerock chris- 208 ###-####
5th floor prerock ok
Rough-in10/13/201710/16/201710/16/2017ACANC
DetailsBen Livingston
5th Floor Pre-Sheetrock Inspection Phone #: ###-#### Inspection requested via web by heather dowd
reschedualed for pm