Final | 12/4/2017 | 12/5/2017 | 12/5/2017 | P | PASS |
Eric Strole
|
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek
|
Pressure Test | 10/4/2017 | 10/5/2017 | 10/5/2017 | P | PASS |
Chad Schwendiman
|
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek - 20lb gas pass
|
Rough-in | 10/4/2017 | 10/5/2017 | 10/5/2017 | P | PASS |
Chad Schwendiman
|
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek
|
Rough-in | 10/4/2017 | 10/4/2017 | 10/4/2017 | P | FAIL |
Brian Scoles
|
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- need to mastic supply boot in floor by front door- b vent needs 1" clearance to plastic 2nd floor in shaft above stairs- need framing completed around duct work 2nd floor NW corner above stairs on supply run that misses truss- left correction notice front window
|
Pressure Test | 10/4/2017 | 10/4/2017 | 10/4/2017 | P | FAIL |
Brian Scoles
|
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- gauge below 20
|