Final | 2/15/2018 | 2/16/2018 | 2/16/2018 | A | PASS |
Eric Strole
|
|
|
Inspection requested via web by Konrad Swartz
|
Conference | 2/13/2018 | 2/15/2018 | 2/15/2018 | A | PASS |
Eric Strole
|
|
|
Duct witness 9am Inspection requested via web by Konrad Swartz-Duct blast pass.
|
Rough-in | 12/12/2017 | 12/12/2017 | 12/12/2017 | P | PASS |
Brian Scoles
|
|
|
Inspection requested via web by Konrad Swartz- corrections made
|
Rough-in | 12/11/2017 | 12/11/2017 | 12/11/2017 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz 1) b vent needs to extend 6" down below ceiling in furnace closet 2) dryer vent ducting exceeds 35'- reroute or booster fan 3)fresh air to R/A plenum un dersized per manual J 4) flex to master closet pinched at take off- 5)range hood ducting broke at 90 degree el at roof, needs to extend below ceiling and strap accordingly 6) lineset needs ran out
left correction notice front entry window
|
Pressure Test | 12/11/2017 | 12/11/2017 | 12/11/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz- 20 lb gas pass-
|
Rough-in | 12/7/2017 | 12/8/2017 | 12/8/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz- need approved manual J onsite for inspection
|