Final | 3/14/2018 | 3/14/2018 | 3/14/2018 | P | PASS |
Ben Livingston
|
|
|
Thanks again! Inspection requested via web by Floyd Floyd Peek
|
Final | 3/13/2018 | 3/13/2018 | 3/13/2018 | A | FAIL |
Ben Livingston
|
|
|
Call Max if you need anything ###-#### Thank you! Inspection requested via web by Floyd Floyd Peek all condensate piping needs to be ancored to structure, fresh air needs to be insulated
|
Rough-in | 12/22/2017 | 12/22/2017 | 12/22/2017 | P | PASS |
Ben Livingston
|
|
|
Bryan Phone #: ###-####
|
Rough-in | 12/13/2017 | 12/14/2017 | 12/14/2017 | P | NR |
Ben Livingston
|
|
|
contractor provided proof the dryers can run the lengths shown, work not complete
|
Rough-in | 12/11/2017 | 12/11/2017 | 12/12/2017 | P | PASS |
Ben Livingston
|
|
|
This is ready for any time. Call Max with Capital City ###-#### or Art with TPI construction ###-#### Art will be on the Job. Thank you! Inspection requested via web by Floyd Floyd Peek
|
Rough-in | 12/8/2017 | 12/8/2017 | 12/8/2017 | A | FAIL |
Ben Livingston
|
|
|
If you need anything or would like us to meet you on the job site. call me or Max at ###-#### Inspection requested via web by Floyd Floyd Peek dryer vents are to long to many 90s, need to be straped every 4ft
|