Final | 2/13/2018 | 2/14/2018 | 2/14/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- final ok
|
Conference | 1/17/2018 | 1/18/2018 | 1/18/2018 | A | PASS |
Brian Scoles
|
|
|
w d blast 11:45 a,m Phone #: ###-#### Inspection requested via web by dannyel chaloupka- duct blast test pass loss 55 cfm
|
Rough-in | 1/2/2018 | 1/3/2018 | 1/3/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- R/I ok- unit in attic
|
Rough-in | 12/29/2017 | 1/2/2018 | 1/2/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- need to insulate supply air bare metal in attic at furnace- need to insulate filter box 3 sides excluding access door- need to provide ladder to access furnace location in attic- left correction notice front window
|
Pressure Test | 12/29/2017 | 1/2/2018 | 1/2/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- 20lb gas pass
|