Final | 2/9/2018 | 2/12/2018 | 2/12/2018 | A | PASS |
Brian Scoles
|
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- TI final ok- card signed
|
Conference | 2/1/2018 | 2/2/2018 | 2/2/2018 | A | DONE |
Brian Scoles
|
|
|
Water Heater Venting Consultation - call jeremy Phone #: ###-#### Inspection requested via web by Brandon Sorensen- went over routing for water heater flue- needs to be 3' higher than fresh air intake within 10'
|
Rough-in | 1/4/2018 | 1/5/2018 | 1/5/2018 | A | PART |
Brian Scoles
|
|
|
cover inspection - call jeremy Phone #: ###-#### Inspection requested via web by Brandon Sorensen- duct and sealing ok- need to verify all materials in plenum need to be rated material
|