Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC18-00127
StatusFinaled
Name INTEGRITY HEATING & AIR
Site Address 8717 W CORY LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: Install new complete HVAC in new residential construction home with gas piping
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/23/20184/24/20184/24/2018PPASS
DetailsBrian Scoles
code is 6175 Phone #: ###-#### Inspection requested via web by Terek Worley- final ok both units
Final4/12/20184/13/20184/13/2018AFAIL
DetailsBrian Scoles
garage code 6175 Phone #: ###-#### Inspection requested via web by Terek Worley- need air balance report onsite- rest is good
Final3/29/20183/30/20183/29/2018ACANC
DetailsBrian Scoles
garage code 6175 Phone #: ###-#### >> Inspection requested via web by Terek Worley Inspection cancelled from web by: Terek Worley
Final3/27/20183/28/20183/28/2018AFAIL
DetailsBrian Scoles
garage code is 6175 Phone #: ###-#### Inspection requested via web by Terek Worley- need duct blast completed- need air balance report onsite- garage access code did not work on south unit- concrete was being poured at both addresses
Rough-in1/30/20181/31/20181/31/2018APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Terek Worley- R/I ok
Pressure Test1/31/20181/31/20181/31/2018APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass both units
Rough-in1/26/20181/29/20181/29/2018AFAIL
DetailsBrian Scoles
Inspection requested via web by Terek Worley- 6" fresh air in both unit need to be ran to R/A plenum at furnace not R/A air can
Rough-in1/25/20181/26/20181/26/2018PCANC
DetailsBrian Scoles
>> Inspection requested via web by Terek Worley Inspection cancelled from web by: Terek Worley
Rough-in1/25/20181/26/20181/25/2018ACANC
DetailsBrian Scoles
>> Inspection requested via web by Terek Worley Inspection cancelled from web by: Terek Worley
Rough-in1/24/20181/25/20181/25/2018AFAIL
DetailsBill VanDegrift
Inspection requested via web by Terek Worley-
1) provide approved ACCA reports
2) 2x 20# gas tests ok